MODEL M FRAME STYLE 

SPRAY NOZZLES

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Form No. F_011594    21.08.04     Rev 21.2

Page 3 of 5

Approval Chart

Frame Style Spray Nozzles

2

 

Open or Automatic

Base Part Number

(Specify Open

 

or Automatic)

Pattern

Thread Size

Nominal Orifice

Nominal

 

K-Factor

Overall Length

Listings and Approvals

4

(Refer also to Design 

Criteria on page 4.)

NPT

BSP

Inches

mm

U.S.

metric

3

Inches

mm

cULus

5

NYC

6

1/2” (13 mm) Orifice

21365

60°

1/2”

15 mm

1/2”

13 mm

5.6

80

2-11/16

68.3

A1, B1

A1, B1

21366

90°

1/2”

15 mm

1/2”

13 mm

5.6

80

2-9/16

65.1

A1, B1

A1, B1

21367

120°

1/2”

15 mm

1/2”

13 mm

5.6

80

2-17/32

64.3

A1, B1

A1, B1

21368

150°

1/2”

15 mm

1/2”

13 mm

5.6

80

2-1/2

63.5

A1, B1

A1, B1

7/16” Orifice

21369

60°

1/2”

15 mm

7/16”

--

4.2

60

2-11/16

68.3

A1, B1

A1, B1

21370

90°

1/2”

15 mm

7/16”

--

4.2

60

2-9/16

65.1

A1, B1

A1, B1

21371

120°

1/2”

15 mm

7/16”

--

4.2

60

2-17/32

64.3

A1, B1

A1, B1

21372

150°

1/2”

15 mm

7/16”

--

4.2

60

2-1/2

63.5

A1, B1

A1, B1

3/8” (10 mm) Orifice

21373

60°

1/2”

15 mm

3/8”

10 mm

2.8

40

2-11/16

68.3

A1, B1

A1, B1

21374

90°

1/2”

15 mm

3/8”

10 mm

2.8

40

2-9/16

65.1

A1, B1

A1, B1

21375

120°

1/2”

15 mm

3/8”

10 mm

2.8

40

2-17/32

64,3

A1, B1

A1, B1

21376

150°

1/2”

15 mm

3/8”

10 mm

2.8

40

2-1/2

63.5

A1, B1

A1, B1

5/16” Orifice

7

21377

60°

1/2”

15 mm

5/16”

--

1.9

27

2-11/16

68.3

A1, B1

A1, B1

21378

90°

1/2”

15 mm

5/16”

--

1.9

27

2-9/16

65.1

A1, B1

A1, B1

21379

120°

1/2”

15 mm

5/16”

--

1.9

27

2-17/32

64.3

A1, B1

A1, B1

21380

150°

1/2”

15 mm

5/16”

--

1.9

27

2-1/2

63.5

A1, B1

A1, B1

1/4” Orifice

7

21381

60°

1/2”

15 mm

1/4”

--

1.4

20

2-11/16

68.3

A1, B1

A1, B1

21382

90°

1/2”

15 mm

1/4”

--

1.4

20

2-9/16

65.1

A1, B1

A1, B1

21383

120°

1/2”

15 mm

1/4”

--

1.4

20

2-17/32

64.3

A1, B1

A1, B1

21384

150°

1/2”

15 mm

1/4”

--

1.4

20

2-1/2

63.5

A1, B1

A1, B1

Approved Temperature Ratings

A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F 

(141 °C)

B - Open (glass bulb and pip cap removed)

Approved Finishes

1 - Brass and Black PTFE for use on water-based deluge and water 

spray systems.

Footnotes

Base part number is shown. When ordering, specify either open or automatic. For complete part number, see current Viking price schedule.

The spray nozzle deflector is identified with the U.S. K-Factor, spray angle, and temperature rating.

Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any 

additional approvals.

Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.

Accepted for use, City of New York Department of Buildings, MEA 89-92-E, Vol. 29.

The orifice is bushed.

Содержание M

Страница 1: ...ULus listed as corrosion resistant as indicated in the Approval Chart 2 LISTINGS AND APPROVALS cULus Listed Category VGYZ NYC Approved MEA 89 92 E Volume 29 NOTE International approval certificates are available upon request Refer to the Approval Chart and Design Criteria for cULus listing requirements that must be followed 3 TECHNICAL DATA Specifications Minimum Operating Pressure 7 PSI 0 5 bar R...

Страница 2: ...ned to be installed in accordance with recognized installation standards Deviation from the standards or any alteration to the nozzle after it leaves the factory including but not limited to painting plating coating or modification may render the unit inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation TABLE 1 AVAILABLE SPRINKLER TEMPERATURE RAT...

Страница 3: ...mm 2 8 40 2 17 32 64 3 A1 B1 A1 B1 21376 150 1 2 15 mm 3 8 10 mm 2 8 40 2 1 2 63 5 A1 B1 A1 B1 5 16 Orifice7 21377 60 1 2 15 mm 5 16 1 9 27 2 11 16 68 3 A1 B1 A1 B1 21378 90 1 2 15 mm 5 16 1 9 27 2 9 16 65 1 A1 B1 A1 B1 21379 120 1 2 15 mm 5 16 1 9 27 2 17 32 64 3 A1 B1 A1 B1 21380 150 1 2 15 mm 5 16 1 9 27 2 1 2 63 5 A1 B1 A1 B1 1 4 Orifice7 21381 60 1 2 15 mm 1 4 1 4 20 2 11 16 68 3 A1 B1 A1 B1 ...

Страница 4: ...orrosion resistant sprinklers and spray nozzles must be installed when subject to corrosive atmospheres When installing corrosion resistant nozzles take care not to damage the corrosion resistant coating F Spray nozzles must be installed after the piping is in place to prevent mechanical damage G Sprinklers and spray nozzles must be protected from mechanical damage Where open sprinklers are used c...

Страница 5: ...nstallation standards require sprinklers to be tested and if necessary replaced after a specified term of service Refer to NFPA 25 and the Authority Having Jurisdiction for the specified period of time after which testing and or replacement is required Never attempt to repair or reassemble a sprinkler Sprinklers that have operated cannot be reassembled or re used but must be replaced When replacem...

Страница 6: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 7: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 8: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 9: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 10: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Отзывы: