BULLETIN

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

CARE AND HANDLING 

OF SPRINKLERS

Page 3 of 4

Form No. F_091699     18.10.11    Rev 16.1.P65

GENERAL HANDLING AND STORAGE INSTRUCTIONS:

• 

Do not store in temperatures exceeding 100 °F (38 °C). Avoid direct sunlight and confined areas subject to heat.

• 

Protect sprinklers and cover assemblies during storage, transport, handling, and after installation. 

-- Use original shipping containers. 

-- Do not place sprinklers or cover assemblies loose in boxes, bins, or buckets.

• 

Keep the sprinkler bodies covered with the protective sprinkler cap any time the sprinklers are shipped or handled, during testing of the system, and 

while ceiling finish work is being completed.

• 

Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. 

NOTE:

 The protective cap is 

temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed. 

• 

Do not over-tighten the sprinklers into fittings during installation.

• 

Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation.

• 

Do not attempt to remove drywall, paint, etc., from the sprinklers.

• 

Remove the plastic protective cap from the sprinkler before attaching the cover plate assembly. 

PROTECTIVE CAPS  MUST BE REMOVED FROM 

SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE! 

Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data 

pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www.

vikinggroupinc.com.

 Concealed Sprinkler and Adapter 

Assembly with Protective Cap

CAUTION: CONCEALED COVER ASSEMBLIES ARE FRAGILE!

TO ASSURE SATISFACTORY PERFORMANCE OF THE PRODUCT, HANDLE WITH CARE

.

 Cover Plate Assembly 

(Pendent Cover 12381 shown)

 Concealed Sprinkler and Adapter 

Assembly (Protective Cap Removed)

Содержание M

Страница 1: ...ULus listed as corrosion resistant as indicated in the Approval Chart 2 LISTINGS AND APPROVALS cULus Listed Category VGYZ NYC Approved MEA 89 92 E Volume 29 NOTE International approval certificates are available upon request Refer to the Approval Chart and Design Criteria for cULus listing requirements that must be followed 3 TECHNICAL DATA Specifications Minimum Operating Pressure 7 PSI 0 5 bar R...

Страница 2: ...ned to be installed in accordance with recognized installation standards Deviation from the standards or any alteration to the nozzle after it leaves the factory including but not limited to painting plating coating or modification may render the unit inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation TABLE 1 AVAILABLE SPRINKLER TEMPERATURE RAT...

Страница 3: ...mm 2 8 40 2 17 32 64 3 A1 B1 A1 B1 21376 150 1 2 15 mm 3 8 10 mm 2 8 40 2 1 2 63 5 A1 B1 A1 B1 5 16 Orifice7 21377 60 1 2 15 mm 5 16 1 9 27 2 11 16 68 3 A1 B1 A1 B1 21378 90 1 2 15 mm 5 16 1 9 27 2 9 16 65 1 A1 B1 A1 B1 21379 120 1 2 15 mm 5 16 1 9 27 2 17 32 64 3 A1 B1 A1 B1 21380 150 1 2 15 mm 5 16 1 9 27 2 1 2 63 5 A1 B1 A1 B1 1 4 Orifice7 21381 60 1 2 15 mm 1 4 1 4 20 2 11 16 68 3 A1 B1 A1 B1 ...

Страница 4: ...orrosion resistant sprinklers and spray nozzles must be installed when subject to corrosive atmospheres When installing corrosion resistant nozzles take care not to damage the corrosion resistant coating F Spray nozzles must be installed after the piping is in place to prevent mechanical damage G Sprinklers and spray nozzles must be protected from mechanical damage Where open sprinklers are used c...

Страница 5: ...nstallation standards require sprinklers to be tested and if necessary replaced after a specified term of service Refer to NFPA 25 and the Authority Having Jurisdiction for the specified period of time after which testing and or replacement is required Never attempt to repair or reassemble a sprinkler Sprinklers that have operated cannot be reassembled or re used but must be replaced When replacem...

Страница 6: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 7: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 8: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 9: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 10: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Отзывы: