TECHNICAL DATA

August 1, 2008

The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058

Telephone:  269-945-9501 Technical Services 877-384-5464  Fax:  269-945-4495  Email:  [email protected]

FLAT SPRAY PENDENT 

SPRINKLERS VK920 (K80) 

AND VK922 (K115)

6.  INSPECTIONS, TESTS AND MAINTENANCE

NOTICE:

 The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For mini-

mum maintenance and inspection requirements, refer to the appropriate standard that describes care and maintenance of sprinkler 
systems. In addition, the Authority Having Jurisdiction may have additional maintenance, testing, and inspection requirements that 
must be followed.

A. Sprinklers must be inspected on a regular basis for corrosion, mechanical damage, obstructions, paint, etc. The frequency of 

the inspections may vary due to corrosive atmospheres, water supplies, and activity around the device.

B. Sprinklers that have been painted, caulked, or mechanically damaged must be replaced immediately. Sprinklers showing signs 

of corrosion shall be tested and/or replaced immediately as required. Installation standards require sprinklers to be tested, and 
if necessary, replaced after a specified term of service. Refer to the installation standards and the Authority Having Jurisdiction 
for the specified period of time after which testing and/or replacement is required. Sprinklers that have operated cannot be reas-
sembled or re-used, but must be replaced. When replacing sprinklers, use only new sprinklers.

C.  The sprinkler discharge pattern is critical for proper fire protection. Nothing should be hung from, attached to, or otherwise 

obstruct the discharge pattern. All obstructions must be immediately removed or, if necessary, additional sprinklers installed.

D. When replacing existing sprinklers, the system must be removed from service. Refer to the appropriate system description and/

or valve instructions. Prior to removing the system from service, notify all Authorities Having Jurisdiction. Consideration should 
be given to employment of a fire patrol in the affected area.

1. Remove the system from service, drain all water, and relieve all pressure on the piping. 
2. Using the special sprinkler wrench, remove the old sprinkler and install the new unit. Care must be taken to ensure that 

the replacement sprinkler is the proper model and style, with the correct orifice size, temperature rating, and response 
characteristics. A fully stocked spare sprinkler cabinet should be provided for this purpose. Follow instructions in section 4. 
INSTALLATION.

3.  Place the system back in service and secure all valves. Check for and repair all leaks. 

E. Sprinkler systems that have been subjected to a fire must be returned to service as soon as possible. The entire system must 

be inspected for damage and repaired or replaced as necessary. Sprinklers that have been exposed to corrosive products of 
combustion or high ambient temperatures, but have not operated, should be replaced. Refer to the Authority Having Jurisdiction 
for minimum replacement requirements.

7.  AVAILABILITY

Viking Flat Spray Pendent Sprinklers are available through a network of domestic and international distributors. See The Viking 
Corporation web site for the closest distributor or contact The Viking Corporation.

8.  GUARANTEE

For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

Sprinkler 127d

OBSOLETE

Содержание K80

Страница 1: ...ure is measured in kPa divide the metric K factor shown by 10 0 Glass bulb fluid temperature rated to 65 F 55 C Overall Length 2 1 4 58 mm for Sprinkler VK920 2 5 16 59 mm for Sprinkler VK922 Material Standards Frame Casting Brass UNS C84400 Deflector Brass UNS C26000 Bulb Glass nominal 3 mm diameter Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with Teflon Tape Screw Brass ...

Страница 2: ...emperature for the temperature rating used Sprinkler 127b TABLE 1 AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 2 Bulb Color Ordinary 155 F 68 C Red Intermediate 175 F 79 C Yellow Intermediate 200 F 93 C Green Sprinkler Finishes Brass or Chrome Enloy Footnotes 1 The sprinkler temperature rating is stamped on the defl...

Страница 3: ...or shown is for use when pressure is measured in bar When pressure is measured in kPa divide the metric K factor shown by 10 0 3 This chart shows the listings and approvals available at the time of printing Check with the manufacturer for any additional approvals Sprinkler 127c Figure 2 Sprinkler Dimensions H After installation and testing and repairing of all leaks remove the protective shields f...

Страница 4: ... hung from attached to or otherwise obstruct the discharge pattern All obstructions must be immediately removed or if necessary additional sprinklers installed D When replacing existing sprinklers the system must be removed from service Refer to the appropriate system description and or valve instructions Prior to removing the system from service notify all Authorities Having Jurisdiction Consider...

Страница 5: ...between the sprinkler deflector and the top of the suspended ceiling shall be no less than 12 300 mm 2 Intermediate sprinklers in HH occupancies The clearance between the sprinkler deflector and the top of storage shall be not less than 4 100 mm NOTE It shall be ensured that water from sprinklers operating at intermediate levels can penetrate the goods stored The dis tance between goods stored in ...

Страница 6: ...Form No F_072508 THIS PAGE INTENTIONALLY LEFT BLANK New page 127a e issued August 1 2008 O B S O L E T E ...

Отзывы: