TECHNICAL DATA

August 1, 2008

The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058

Telephone:  269-945-9501 Technical Services 877-384-5464  Fax:  269-945-4495  Email:  [email protected]

FLAT SPRAY PENDENT 

SPRINKLERS VK920 (K80) 

AND VK922 (K115)

4.  INSTALLATION

The sprinklers are designed to be installed in accordance with recognized installation standards. Viking Flat Spray Pendent 
Sprinklers must be installed in accordance with the latest edition of Viking technical data, CEA 4001 “Sprinkler Systems Planning 
and Installation” or EN12845 “Automatic Sprinkler Systems - Design, Installation, and Maintenance”, the Authorities Having 
Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards whenever applicable. Deviation from 
the standards or any alteration to the sprinkler after it leaves the factory including, but not limited to: painting, plating, coating, or 
modification, may render the sprinkler inoperative and will automatically nullify the approval and any guarantee made by The Viking 
Corporation.

A. Sprinklers must be handled with care. They must be stored in a cool, dry place in their original shipping container. Never install 

sprinklers that have been dropped or damaged in any way or exposed to temperatures exceeding the maximum ambient tem-
perature allowed (refer to Table 1). Never install any glass-bulb sprinkler if the bulb is cracked or if there is a loss of liquid from 
the bulb. A small air bubble should be present in the glass bulb. Any sprinkler with a loss of liquid from the glass bulb should be 
destroyed immediately. 

B. Wet pipe systems must be provided with adequate heat. 
C. Use care when locating sprinklers near fixtures that can generate heat. Do not install sprinklers where they could be exposed 

to temperatures exceeding the maximum recommended ambient temperature for the temperature rating used.

Sprinkler 127b

TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES

Sprinkler Temperature Classification

Sprinkler Nominal Temperature Rating

1,2

Bulb Color

Ordinary

155 °F (68 °C)

Red

Intermediate

175 °F (79 °C)

Yellow

Intermediate

200 °F (93 °C)

Green

Sprinkler Finishes:

 Brass or Chrome-Enloy

®

Footnotes

1

 The sprinkler temperature rating is stamped on the deflector. 

2

 Sprinklers shall be chosen with a temperature rating close to but not lower than 30 °C above the highest anticipated ambient temperature. 

Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to 
specific installation standards.

Figure 1:  

Standard Sprinkler Wrench 10896W/B

D. The sprinklers must be installed after the piping is in place to 

prevent mechanical damage. Before installing, be sure to have 
the appropriate sprinkler model and style, with the correct orifice 
size, temperature rating, and response characteristics.

E. With the sprinkler contained in the plastic protective shield, 

apply a small amount of pipe-joint compound or tape to the male 
threads only, while taking care not to allow a build-up of com-
pound in the sprinkler orifice.

F. Install the sprinkler on the piping using special sprinkler wrench 

10896W/B only, while taking care not to damage the sprinkler 
operating parts. (Any other type of wrench may damage the unit.) 
DO NOT use the sprinkler deflector to start or thread the sprinkler 
into a fitting.

G. After installation, the entire sprinkler system must be tested. The 

test must be conducted to comply with the Installation Standards. 
Make sure the sprinkler has been properly tightened. If a thread 
leak occurs, normally the unit must be removed, new pipe-joint 
compound or tape applied, and then reinstalled. This is due to the 
fact that when the joint seal is damaged, the sealing compound or 
tape is washed out of the joint. Immediately replace any damaged 
units, using the special sprinkler wrench only.

OBSOLETE

Содержание K80

Страница 1: ...ure is measured in kPa divide the metric K factor shown by 10 0 Glass bulb fluid temperature rated to 65 F 55 C Overall Length 2 1 4 58 mm for Sprinkler VK920 2 5 16 59 mm for Sprinkler VK922 Material Standards Frame Casting Brass UNS C84400 Deflector Brass UNS C26000 Bulb Glass nominal 3 mm diameter Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with Teflon Tape Screw Brass ...

Страница 2: ...emperature for the temperature rating used Sprinkler 127b TABLE 1 AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 2 Bulb Color Ordinary 155 F 68 C Red Intermediate 175 F 79 C Yellow Intermediate 200 F 93 C Green Sprinkler Finishes Brass or Chrome Enloy Footnotes 1 The sprinkler temperature rating is stamped on the defl...

Страница 3: ...or shown is for use when pressure is measured in bar When pressure is measured in kPa divide the metric K factor shown by 10 0 3 This chart shows the listings and approvals available at the time of printing Check with the manufacturer for any additional approvals Sprinkler 127c Figure 2 Sprinkler Dimensions H After installation and testing and repairing of all leaks remove the protective shields f...

Страница 4: ... hung from attached to or otherwise obstruct the discharge pattern All obstructions must be immediately removed or if necessary additional sprinklers installed D When replacing existing sprinklers the system must be removed from service Refer to the appropriate system description and or valve instructions Prior to removing the system from service notify all Authorities Having Jurisdiction Consider...

Страница 5: ...between the sprinkler deflector and the top of the suspended ceiling shall be no less than 12 300 mm 2 Intermediate sprinklers in HH occupancies The clearance between the sprinkler deflector and the top of storage shall be not less than 4 100 mm NOTE It shall be ensured that water from sprinklers operating at intermediate levels can penetrate the goods stored The dis tance between goods stored in ...

Страница 6: ...Form No F_072508 THIS PAGE INTENTIONALLY LEFT BLANK New page 127a e issued August 1 2008 O B S O L E T E ...

Отзывы: