background image

FLAT SPRAY PENDENT 

SPRINKLERS VK920 (K80) 

AND VK922 (K115)

TECHNICAL DATA

August 1, 2008

The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058

Telephone:  269-945-9501 Technical Services 877-384-5464  Fax:  269-945-4495  Email:  [email protected]

1.  DESCRIPTION

Viking Flat Spray Pendent Sprinklers VK920 and VK922 are small, thermosensitive, 
glass-bulb sprinklers intended for installation in accordance with local standards. 
They produce a flatter spray pattern than standard spray sprinklers, allowing them 
to be used with lower clearance above suspended open ceillings, in racks, and 
concealed spaces. Sprinklers VK920 and VK922 are VdS approved with a Brass or 
Chrome-

Enloy

® 

finish, with various temperature ratings, and a nominal K-Factor of 

5.6 (80 metric) or 8.0 (115 metric) to meet design requirements. 

2.  LISTINGS AND APPROVALS

VdS Approved:

 Certificate #

Refer to the Approval Chart on page 127c and Design Criteria on page 127e for VdS
approval requirements that must be followed.

3.  TECHNICAL DATA

Specifi cations:

Available since 2008.
Minimum Operating Pressure: Refer to CEA 4001 or EN12845. 
Maximum Working Pressure: 175 psi (12 bar). 
Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A. Patent No. 4,831,870
Thread size: 1/2” (15 mm) or 3/4” (20 mm) NPT
Nominal K-Factor: 5.6 U.S. (80.6 metric

*

) or 8.0 U.S. (115.2 metric*)

 *Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

 

Glass-bulb fluid temperature rated to -65 °F (-55 °C)

Overall Length: 2-1/4“ (58 mm) for Sprinkler VK920, 2-5/16” (59 mm) for Sprinkler VK922 

Material Standards:

Frame Casting: Brass UNS-C84400 
Deflector: Brass UNS-C26000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400

Ordering Information:

 (Also refer to the current 

Viking price list

.)

Order Flat Spray Pendent Sprinklers VK920 and VK922 by first adding the appropriate suffix for the sprinkler finish and then the 

appropriate suffix for the temperature rating to the sprinkler base part number. 

Finish Suffix: Brass = A, Chrome-Enloy

®

 = F

Temperature Suffix (°F/°C): 155°/68° = B, 175°/79° = D, 200°/93° = E
For example, sprinkler VK920 with a Brass finish and a 155 °F/68 °C temperature rating = Part No. 15111AB

Available Finishes and Temperature Ratings:

 

Refer to Table 1

Accessories:

  (Also refer to the “Sprinkler Accessories” section of the Viking data book.)

Sprinkler Wrench: 

Standard Wrench: Part No. 10896W/B (available since 2000). 

Sprinkler Cabinets:

A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)

Form No. F_072508

Viking Technical Data may be found on 

The Viking Corporation’s Web site at 

http://www.vikinggroupinc.com.

The Web site may include a more recent 

edition of this Technical Data Page.

Sprinkler 127a

New page 127a-e, issued August 1, 2008.

Sprinkler VK920 (K80) and VK922 (K115)

OBSOLETE

Содержание K80

Страница 1: ...ure is measured in kPa divide the metric K factor shown by 10 0 Glass bulb fluid temperature rated to 65 F 55 C Overall Length 2 1 4 58 mm for Sprinkler VK920 2 5 16 59 mm for Sprinkler VK922 Material Standards Frame Casting Brass UNS C84400 Deflector Brass UNS C26000 Bulb Glass nominal 3 mm diameter Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with Teflon Tape Screw Brass ...

Страница 2: ...emperature for the temperature rating used Sprinkler 127b TABLE 1 AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 2 Bulb Color Ordinary 155 F 68 C Red Intermediate 175 F 79 C Yellow Intermediate 200 F 93 C Green Sprinkler Finishes Brass or Chrome Enloy Footnotes 1 The sprinkler temperature rating is stamped on the defl...

Страница 3: ...or shown is for use when pressure is measured in bar When pressure is measured in kPa divide the metric K factor shown by 10 0 3 This chart shows the listings and approvals available at the time of printing Check with the manufacturer for any additional approvals Sprinkler 127c Figure 2 Sprinkler Dimensions H After installation and testing and repairing of all leaks remove the protective shields f...

Страница 4: ... hung from attached to or otherwise obstruct the discharge pattern All obstructions must be immediately removed or if necessary additional sprinklers installed D When replacing existing sprinklers the system must be removed from service Refer to the appropriate system description and or valve instructions Prior to removing the system from service notify all Authorities Having Jurisdiction Consider...

Страница 5: ...between the sprinkler deflector and the top of the suspended ceiling shall be no less than 12 300 mm 2 Intermediate sprinklers in HH occupancies The clearance between the sprinkler deflector and the top of storage shall be not less than 4 100 mm NOTE It shall be ensured that water from sprinklers operating at intermediate levels can penetrate the goods stored The dis tance between goods stored in ...

Страница 6: ...Form No F_072508 THIS PAGE INTENTIONALLY LEFT BLANK New page 127a e issued August 1 2008 O B S O L E T E ...

Отзывы: