background image

Con cealed Sprin kler can be ver i fied
by check ing the fus ible link for the fol -
low ing iden ti fi ca tion scheme:

Stan dard Re sponse:  No stripe or

dot.

Quick Re sponse: Pur ple stripe or

dot.

EC & QREC: Yel low stripe or dot.

Fol low in struc tions pro vided in  “IN -

STAL LA TION” para graph 

7.

6. Place the sys tem back in ser vice and

se cure all valves. Check the re placed
sprin klers and re pair all leaks.

E. Sprin kler sys tems that have been sub -

jected to a fire must be re turned to ser -
vice as soon as pos si ble. The en tire
sys tem must be in spected for dam age

and re paired or re placed as nec es sary. 
Sprin klers that have been ex posed to
cor ro sive prod ucts of com bus tion or
high am bi ent tem per a tures, but have
not op er ated, should be re placed. Re -
fer to the Au thor ity Hav ing Ju ris dic tion
for min i mum re place ment re quire -
ments. 

Form No. F_050493

Sprin kler 58 d

May 25, 2000

TECH NI CAL DATA

 

HO RI ZON

®

 

 MI RAGE

®

QUICK RE SPONSE

EX TENDED COV ER AGE

CON CEALED SPRIN KLERS

Re places page 58 a-d, dated Oc to ber 20, 1999. (These
sprin klers are avail able with 220 °F tem per a ture rat ing).

Sprin kler Tem per a ture

Clas si fi ca tion

Nom i nal Tem per a ture Rat ing

1

High est Am bi ent Tem per a ture

Al lowed at Ceil ing

2

Re quired Cover As sem bly

Tem per a ture Rat ing

Or di nary

165 °F (74 °C)

100 °F (38 °C)

165 °F (74 °C)

Intermediate

220 °F (104 °C)

150 °F (65 °C)

165 °F (74 °C)

Ap proval Chart

Model B-1 Stan dard Or i fice Ho ri zon

®

 Mi rage

®

 Quick

Re sponse Ex tended Cov er age Con cealed Pen dent Sprin kler

Sprin kler Part

Num ber

3

NPT Thread

Size

Max i mum Areas

of Cov er age

5

Nom i nal

K-Factor

Min i mum Wa ter

Sup ply Re quire ments

5

List ings and  Ap provals

4

UL

7

C-UL

7

NYC

8

Inches mm

Length x Width

U.S. met ric

6

08498

1/2

15

16 ft. x 16 ft.

(4,9 m x 4,9 m)

5.5

7,9

26 gpm @ 22.3 psi

(98,4 L/min @ 155 kPa)

A1

A1

A1

08498

1/2

15

18 ft. x 18 ft.

(5,5 m x 5,5 m)

5.5

7,9

33 gpm @ 36.0 psi

(124,9 L/min @ 250 kPa)

A1

A1

A1

08498

1/2

15

20 ft. x 20 ft.

(6,1 m x 6,1 m)

5.5

7,9

Listed for this spac ing as stan dard re sponse ex tended cov er age

sprin klers. See ex tended cov er age sprin kler page 87 a-d.

Model B-2 Large Or i fice Ho ri zon

®

 Mi rage

®

 Quick Re sponse Ex tended Cov er age Con cealed Pen dent Sprin klers

Sprin kler Part

Num bers

3

NPT Thread

Size

Max i mum Areas

of Cov er age

5

Nom i nal

K-Factor

Min i mum Wa ter

Sup ply Re quire ments

5

Listings

4

Length x Width

UL

7

C-UL

7

NYC

Inches mm

U.S. met ric

6

10485

1/2

15

16 ft. x 16 ft.

(4,9 m x 4,9 m)

8.0

11,5

26 gpm @10.6 psi

(98,4 L/min @ 75 kPa)

A1

A1

10680

3/4

20

10485

1/2

15

18 ft. x 18 ft.

(5,5 m x 5,5 m)

8.0

11,5

33 gpm @ 17.0 psi

(124,9 L/min @ 118 kPa)

A1

A1

10680

3/4

20

10485

1/2

15

20 ft. x 20 ft.

(6,1 m x 6,1 m)

8.0

11,5

Listed for this spac ing as stan dard re sponse ex tended cov er age

sprin klers. See ex tended cov er age sprin kler page 87 a-d.

10680

3/4

20

Avail able Tem per a ture Rat ings

9

A - 165 °F (74 °C)  
B - 220 °F (104 °C)

Ap proved Cover Fin ishes

1 - Bright Brass, Pol ished Chrome, Painted White, Painted Ivory, or Painted Black

10

Foot notes

1

 Tem per a ture rat ing of the Ho ri zon

®

 Mi rage

®

 Con cealed Sprin kler is stamped on the sprin kler body.

2

 Based on NFPA-13. Other lim its may ap ply, de pend ing on fire load ing, sprin kler lo ca tion, 

and other re quire ments of the Au thor ity Hav ing Ju ris -

dic tion. Re fer to spe cific in stal la tion stan dards.

3

 Base part num ber is shown. For com plete part num ber, re fer to Vi king's cur rent price list.

4

 This chart shows list ings and ap prov als avail able at time of print ing. Other ap prov als may  be in pro cess. Check with the man u fac turer for ad di -

tional ap prov als.

5

 For ar eas of cov er age smaller than shown, use the "Min i mum Wa ter Sup ply Re quire ment" for  the next larger "Area of Cov er age" listed for the

sprin kler used. The dis tance from sprin klers to walls shall not ex ceed one-half the sprin kler  spac ing in di cated for the "Min i mum Wa ter Sup ply
Re quire ment" used. 

6

 Met ric K-factor shown is for use when pres sure is mea sured in kPa. When pres sure is mea sured in BAR, multiply the met ric K-factor shown by 10.0. 

7

 List ing is lim ited to Light-Hazard oc cu pancies with smooth, flat, hor i zon tal ceil ings.

8

 Ac cepted for use, City of New York De part ment of Build ings, MEA 89-92, Volume IX.

9

 Avail able tem per a ture rat ings are 165 °F (74 °C) and 220 °F (104 °C), how ever, the 220 °F (104 °C) tem per a ture rated sprin kler has no List ings

or Approvals at the time of this print ing.

10

Other paint col ors are avail able on re quest with the same List ings and Ap provals as the stan 

dard paint finishes.

Ta ble 

1

                         

 Tem per a ture              

KEY

                   Fin ish

  A1X

        Es cutch eon (if ap pli ca ble)

OBSOLETE

Содержание HORIZON MIRAGE

Страница 1: ...t Hazard occupancies with smooth flat horizontal ceilings only Refer to Table 1 on page 58 d Rated to 175 psi 1 207 kPa water working pressure Factory tested pneumatically to 95 psi 655 kPa Spring U S A Patent No 4 570 720 Thread Sizes Part Nos 08498 and 10485 1 2 15 mm NPT Part No 10680 3 4 20 mm NPT Orifice Sizes Part No 08498 Standard Orifice Part Nos 10485 and 10680 Large Orifice K factors Par...

Страница 2: ...nklers should be destroyed immedi ately C Horizon Mirage Quick Response Concealed Sprinklers must be installed in neutral or negative pressure ple nums only D Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be ex posed to temperatures that exceed the maximum recommended ambient tem peratureforthetemperature ratingused E Horizon Mira...

Страница 3: ...ted or me chanically damaged must be replaced immediately Sprinklers showing signs of corrosion shall be tested and or re placed immediately as required Instal lation standards require sprinklers to be tested and if necessary replaced immediately after a specified term of service Refer to the installation stan dards and the Authority Having Juris diction for the specified period of time after whic...

Страница 4: ...s Sprinkler Part Numbers3 NPT Thread Size Maximum Areas of Coverage5 Nominal K Factor Minimum Water Supply Requirements5 Listings4 Length x Width UL7 C UL7 NYC Inches mm U S metric6 10485 1 2 15 16 ft x 16 ft 4 9 m x 4 9 m 8 0 11 5 26 gpm 10 6 psi 98 4 L min 75 kPa A1 A1 10680 3 4 20 10485 1 2 15 18 ft x 18 ft 5 5 m x 5 5 m 8 0 11 5 33 gpm 17 0 psi 124 9 L min 118 kPa A1 A1 10680 3 4 20 10485 1 2 ...