TSFC 12-2 User Manual
Vighnaharta Technologies Pvt. Ltd. Page
13
of
26
•
Enter all external cables via preformed cable entry holes located at top of the panel.
•
When the installation of all the cables has been completed, clean the interior of the enclosure
ensuring all masonry debris and drilling swords are removed.
2.3
Panel Wiring
The following diagram shows basic components of Fire Panel System. It consists of various smoke
and heat detectors, AC power source, Notification devices like siren or sounder, etc
WARNING:
Several different sources of power can be connected to this panel. Disconnect all sources of power
before servicing. The panel and associated equipment may be damaged by removing and / or
inserting cards, modules or inter connecting while this unit is energized.
Primary Power source (AC) and Earth Ground Connection:
AC Power connections are made inside the control panel cabinet. A separate Earth Ground
connection must be made to ensure the proper panel operation and lightening and transient
protection.
Standby Power Source (Batteries):
Use one 12V/1.2Ah sealed lead acid type Battery. Observe polarity when connecting the battery.
Connect the battery to the provided cable. The battery charger is current - limited and capable of
recharging sealed lead acid type batteries up to 1.2Ah.
Display
Keypad
Zone 1
Zone 2
Two IDC
3 PFC Output
2 for Fire
1 for Fault
1 NAC
(Siren Output-500mA)
TSFC 12-2 Panel
WiFi
Connectivity
230VAC/50Hz
Supply With
Battery Backup