TSFC 12-2 User Manual
Vighnaharta Technologies Pvt. Ltd. Page
9
of
26
•
Password protected menus
•
Up to 15 scrolling events capacity
•
Cloud Connectivity through Wi-Fi
1.3
Technical Specifications
Power Supply
230V AC Input 50/60 Hz
Input
Initiating Device Circuit (IDC)
•
Voltage: 12 VDC
•
End of Line:
820Ω,
1 W
Indication
Front panel LED indications
•
SYSTEM ON
•
MAINS FAIL
•
BATTERY FAULT
•
NAC FAULT
•
Siren SILENCE
•
WiFi
•
Zone Fault
•
Walk Test Mode
•
Zone Bypass
•
Fire
•
WALK TEST
16 x 2 LCD Display Indication
Zone fire status, fault status, configuration menus, Etc
Buzzer Indication
Fire, Fault, Walk Test Fire, Key press acknowledge
Output
NAC (Siren Output)
Voltage: 12 VDC, Current: 500 mA
Optional PFC Relay outputs: 3
Dimensions
237 x 217 x 42 (L x H x W)
Operating
Temperature
0
0
C to +50
0
C
Humidity
5 to 90% Rh
Weight
Approx. 1.2Kg (without battery)
Enclosure
Plastic Enclosure