TS21I_IR_CO2 User Manual
Vighnaharta Technologies Pvt Ltd Page
4
of
13
Technical Specifications
Power Supply
Input- 24 VDC, 200mA
Input
4 Magnetic keys, DI (Normally Closed)
Indication
LED indication for following status:
1. Power ON: green LED
2. Low Alarm: yellow LED
3. High Alarm: red LED
4. Fault condition : orange LED
Output
1.Three potential free relay output with NO / NC
Selectable
2. 0-5V OR 0-10V analog output
3. 4-20mA current output
Operating Temperature
-10C°to 55C°
Humidity
0 to 95 % Rh.
RS485 Interface
Modbus RTU Protocol
Enclosure
Aluminium casting
Installation Procedure
Prerequisites:
The convenient location for mounting the system must be finalized.
•
TS21I_IR_CO2 unit
•
Power supply adapter ( Optional)
•
mounting screws
•
User manual
•
Screw driver
•
Allen Key set
To install the unit at the user premises
1.
Run all desired power, siren and hardware contact wires to the panel location.
2.
Level the cabinet on sturdy wall and mark the mounting holes with a pencil.
Installation precautions
•
This detector head in the flame proof enclosure must be installed near the CO2 gas cylinders or
at the joints of gas carrying pipes.
•
The detector must face down to cater for heavier than air gases.
•
CO2 is heavier than air, it has tendency to settle down. Hence, if you are using CO2 cylinder,
install the unit up to 30cm above floor.
Don’ts
•
Don’t use the unit in direct sunlight.
•
Don’t expose the sensor to gas concentration higher than its prescribed range.
•
Don’t immerse the unit in any liquid.
•
Don’t attempt to clean the detector from inside.
•
Don’t open the flameproof enclosure when gas is present.
•
Don’t switch high voltage or power loads through the relay, use only as potential free contacts.