background image

TS21I_IR_CO2 User Manual 

Vighnaharta Technologies Pvt Ltd                                      Page 

12

 of 

13

 

 

 

Function names in the menu 

Process Steps 

 

from 

following 

option 

2.4(2400), 

9.6(9600), 

19.2(19200). 

5.

 

Press 

Enter

  key  to  save  the  settings  or  press 

Escape

  key  to  return  to  previous  menu  without 

saving the settings. 

4. 

PArt 
 

 

User can set Parity either None, Even, Odd.   

1.

 

Press 

ENTER

 to go in main menu. 

2.

 

Use 

Down

 key to select ‘

PArt

’ function. 

3.

 

To go into ‘

PArt

’ function, again press 

ENTER

 key.  

4.

 

Use 

Up

  or 

Down

  keys  to  select  any  parity  from 

following  option  ‘

nonE

’  (None),  ‘

EuEn

’  (Even),   

‘_

odd

’ (Odd). 

5.

 

Press 

Enter

  key  to  save  the  settings  or  press 

Escape

  key  to  return  to  previous  menu  without 

saving the settings. 

5. 

Addr 
 

 

User can set device address from 1 to 254.   

1.

 

Press 

ENTER

 to go in main menu. 

2.

 

Use 

Down

 key to select ‘

Addr

’ function. 

3.

 

To go into ‘

Addr

’ function, again press 

ENTER

 key.  

4.

 

Use 

Up

  or 

Down

  keys  to  select  address  from  1  to 

254. 

5.

 

Press 

Enter

  key  to  save  the  settings  or  press 

Escape

  key  to  return  to  previous  menu  without 

saving the settings. 

 
 

Do’s and Don’ts when gas leak occurs 

 
 
Do’s: 

 

If the gas leakage is severe, it is very dangerous for anybody to enter the premises, as 
it causes shortness of breath, headache, nausea, dizziness etc. Call Gas dealer/ turn ON 
exhaust. 

 

 

If there is a minor/moderate gas leakage- Turn off the knob regulators etc, to stop gas 
supply. 

 

Open all doors & windows. 

Don’ts: 

 

Do not panic. 

 

Do not OFF/ON any electrical switch as CO2 is readily flammable gas. 
 

 

Routine Check for TrueSafe TS21I_IR_CO2 

 

To ensure that TrueSafe TS21I_IR_CO2 is in working condition, it is necessary to check 
working of Gas LED by manual testing. 

 

For checking unit’s sensing capability, it is necessary to check the unit once in a month. 

 

Maintenance 

 

Maintenance Guidelines

:  

• The sensor is shipped with a factory calibration. Sensor should be calibrated 6 months from 
purchase date. 
 • Calibrate the detector at least once every 1year.  
• Calibration should be performed with certified calibration gas. Calibration kits and replacement 
cylinders are available from Calibration Technologies.  
• All tests and calibrations must be logged.  
• Always disconnect power at the controller before performing any wiring at the sensor. 

Содержание TS21 I IR CO2

Страница 1: ...n Website http www vighnaharta in Prepared By MDC Approved By JG Doc No TS21I_IR_CO2_UM_2_0 Rev No 2_0 Eff Date 23 05 2020 TS21I_IR_CO2 USER MANUAL Mfg By Vighnaharta Technologies Pvt Ltd 2nd Floor Karanjkar Estate S N 11 11 Nanded Gaon Pune 411041 Contact no 919011033259 Landline Sales 919011033260 Email sales vighnaharta in Website http www vighnaharta in ...

Страница 2: ...21I_IR_CO2 User Manual Vighnaharta Technologies Pvt Ltd Page 2 of 13 Table of Contents Overview III Technical Specifications IV Installation Procedure IV Operation VI Menu Details X Calibration process XI ...

Страница 3: ...s CO2 sensors can be used to monitor the quality of air and the tailored need for fresh air respectively Measuring CO2 levels indirectly determines how many people are in a room and ventilation can be adjusted accordingly Salient Features Detection Gas CO2 carban dioxide Gas Detection Range v v 0 to 5 v v with user defined high and low alarm level Four digit seven segment LED display for v v level...

Страница 4: ...w driver Allen Key set To install the unit at the user premises 1 Run all desired power siren and hardware contact wires to the panel location 2 Level the cabinet on sturdy wall and mark the mounting holes with a pencil Installation precautions This detector head in the flame proof enclosure must be installed near the CO2 gas cylinders or at the joints of gas carrying pipes The detector must face ...

Страница 5: ...NO Connector CON2 Pin No Description 1 D RS 485 data 2 D RS485 data 3 C ve current Output 4 C ve current Output 5 A O P ve analog output voltage 6 A O P ve analog output voltage 7 DI Digital Input 8 VCC 9 GROUND Connecting wires Take out the wires from supply relay output and RS 485 port Make the connections for relay and RS 485 as mentioned in above table Take out wires from output and connect it...

Страница 6: ...es four magnetic keys which operate using single magnetic stylus to do settings like low high alarm levels relay output type and so on Front panel of typical TS21I_IR_CO2 is shown as below Relay Settings TS21I_IR_CO2 has threerelay outputs Relay1 for low alarm condition Relay2 for high alarm condition and Relay3 for Fault operation User can use it as a NO or NC type output using the respective jum...

Страница 7: ...n set NO type contact or NC type of contact For Relay1 JP1 Jumper between pin 1 and 2 Relay1 will be NC type Jumper between pin 2 and 3 Relay1 will be NO type JP1 For Relay2 JP2 Jumper between pin 1 and 2 Relay2 output will be NC type Jumper between pin 2 and 3 Relay2 output will be NO type JP2 For Relay3 JP3 Jumper between pin 1 and 2 Relay3 will be NC type Jumper between pin 2 and 3 Relay3 will ...

Страница 8: ...slave address using Interaction Maximum of 254 slave IDs can be set using Interaction Refer Interaction details Note If user set wrong slave address then unit may not be able to communicate with gas detection panel Modbus Communication Default Settings for TS21I_IR_CO2 Baud Rate 9600 bps Parity Even Relay 1 NO O P PULSE type Relay 2 NO O P PULSE type Relay 3 NO O P PULSE type Output Voltage 0 10Vo...

Страница 9: ...y remains on for 5sec If relay2 output is latch type relay remains on till the unit is reset 3 F Alarm When supplay goes below 19V or above 29V and also sensor status open or short Orange LED turns ON till unit is reset If relay3 output is pulse type relay remains on for 5sec If relay3 output is latch type relay remains on till the unit is reset 4 LED Display Four digits Seven Segment LED display ...

Страница 10: ...H type 1 Press ENTER to go in main menu 2 Use Down Key to select oP L function 3 To go into oP L function again press ENTER key 4 Use Up and Down keys to select PULSE or LATCH type for Relay1 output 5 Press Enter key to save the settings or press Escapekey to return to previous menu without saving the settings 4 oP h Output High User can set Relay2 output as either PULSE or LATCH type 1 Press ENTE...

Страница 11: ...ress ENTER key to save the count 9 Press ESCAPE key to exit from Configuration mode and remain in Idle or Scan mode 2 o2ZC Output 2 Zero calibration This is a calibration function used to calibrate voltage output for 0V o2SC Output 2 Span calibration This is a calibration function used to calibrate voltage output for 5 10V depending on voltage range set in menu A oP 1 Go to menu A oP 2 Press Up or...

Страница 12: ...thout saving the settings Do s and Don ts when gas leak occurs Do s If the gas leakage is severe it is very dangerous for anybody to enter the premises as it causes shortness of breath headache nausea dizziness etc Call Gas dealer turn ON exhaust If there is a minor moderate gas leakage Turn off the knob regulators etc to stop gas supply Open all doors windows Don ts Do not panic Do not OFF ON any...

Страница 13: ...nnection therewith No statement or recommendation contained herein shall have force or effect unless in an agreement signed by officers of manufacturer or seller Seller s and manufacturer s only obligation shall be limited to replace the product which is proved to be having manufacturing defect and returned with in the warranty period Terms Of Warranty 1 All models of TrueSafe detectors are warran...

Отзывы: