Vitotronic 300, GW2B Installation and Service

DHW Tank Temperature Control

Functions
Time program

An automatic or an individual time program may be 

selected for DHW heating and the DHW recirculation 

pump.
Compared with the heating circuit heatup phase, 

DHW heating starts 30 min earlier in automatic mode.
The individual time program enables up to 4 time 

phases per day to be set for DHW heating and the DHW 

recirculation pump for every day of the week.
All DHW tank heating sequences will be completed 

independently of the time program. 

In conjunction with coding address “7F” in the “General” 

group

 

H

Detached house 

Code “7F:1”:

– Automatic mode

    The heating times for heating circuit 1 are applied    

to systems with two or three heating circuits.

– Individual time program

    The time phases for DHW heating and the DHW 

recirculation pump have the same effect on all heating 

circuits.

 

H

Apartment building

Code “7F:0”:

  – Automatic mode

      For systems with two or three heating circuits,      

the heating times for the relevant heating circuit will 

be applied.

  – Individual time program

      The time phases for DHW heating and the DHW 

recirculation pump can be adjusted individually for 

each heating circuit.

Function Description

Brief description

 

H

The DHW tank temperature control is a constant 

temperature control. This is the result of starting and 

stopping the circulation pump for DHW tank heating. 

The switching differential is ±2.5 K.

 

H

When the DHW tank is heated, a set supply 

temperature is specified that is 20 K higher than the set 

DHW temperature (adjustable via coding address “60”               

in the “DHW” group).

Priority control

 

H

With priority control: (code “A2:2” in the “Heating 

circuit...” group): 

  The set supply temperature is set to 32°F (0°C) during  

  DHW tank heating. 

  The mixing valve closes and the heating circuit pump 

  is switched off.

 

H

Without priority control: 

The heating circuit control unit continues to operate 

with the same set value.

 

H

With modulating priority control in conjunction with 

heating circuits with mixing valve:

  The heating circuit pump remains switched on. The set  

  supply temperature of the heating circuits will be  

  reduced, for as long as the set boiler water temperature  

  has not been reached during DHW tank heating.

  The set supply temperature is determined from the  

 following 

parameters:

  – Outside temperature

  – Differential between the set and the actual boiler  

     water temperature

  – Heating curve slope and shift

  – Setting of coding address “A2” in the “Heating  

     circuit...” group

Содержание VITOTRONIC 300 GW2B

Страница 1: ...pensated digital boiler control units For use with Boiler models VD2A VD2 and CT3 for use by heating contractor Installation and Service Instructions Read and save these instructions for future refere...

Страница 2: ...d related product documentation must be read and followed Failure to do so renders the warranty null and void Licensed professional heating contractor The installation adjustment service and maintenan...

Страница 3: ...ation scheme 22 Mixing valve extension PCB 24 Required code 24 System Example 4 25 Single boiler system with Vitocrossal 25 Equipment required 26 Electrical installation scheme 28 Mixing valve extensi...

Страница 4: ...upply 53 Changing the Language 56 Setting the Date and Time 56 Testing the High Limits Safety Cut out 56 Matching the Coding Addresses to the System Version 57 Checking Actuator and Sensors 58 Adjusti...

Страница 5: ...ontents Connection and Wiring Diagram Type GW2B 120 Sensors 124 Outside Temperature Sensor 125 Flue Gas Temperature Sensor 125 Extension Kit Mixing Valve 126 Extension EA1 Accessory optional 127 Type...

Страница 6: ...onic 300 GW2B Installation and Service 5693 982 04 6 Preparing for Installation Designations in the System Examples In the following system examples the Vitotronic 300 type GW2B is used as the control...

Страница 7: ...em Example 1 Preparing for Installation Single boiler system Boiler with Therm Control Hydraulic installation scheme Note This scheme is a basic example without shut off devices or safety equipment Th...

Страница 8: ...t 2 qW Heating circuit pump M2 Mixing valve extension kit qQ Supply temperature sensor M2 as contact temperature sensor and qE Mixing valve motor M2 or Supply temperature sensor M2 as qQ Contact tempe...

Страница 9: ...eW 3 digital inputs External heating program changeover separately adjustable for heating circuits 1 to 3 External demand External blocking with fault message input Fault message input Short term oper...

Страница 10: ...Vitotronic 300 GW2B Installation and Service 5693 982 04 10 Preparing for Installation System Example 1 continued Electrical installation scheme Main PCB 120V...

Страница 11: ...11 5693 982 04Vitotronic 300 GW2B Installation and Service Preparing for Installation System Example 1 continued Main PCB LV connections...

Страница 12: ...installed downstream via temperature sensor T1 in heating systems with heating circuit control units that are not connected to the boiler control unit via LON Required code 4C 2 General group Use of...

Страница 13: ...allation System Example 2 Single boiler system Boiler with shunt pump for return temperature raising Hydraulic installation scheme Note This scheme is a basic example without shut off devices or safet...

Страница 14: ...on site 8 DHW tank 9 DHW tank temperature sensor STS qP DHW pump UPSB qQ DHW recirculation pump ZP qW Heating circuit 2 qR Heating circuit pump M2 Mixing valve extension kit qE Mixing valve motor for...

Страница 15: ...r mixing valve Close eP Extension EA1 eQ 1 analog input 0 10V Specification of the set boiler water temperature eW 3 digital inputs External heating program changeover separately adjustable for heatin...

Страница 16: ...Vitotronic 300 GW2B Installation and Service 5693 982 04 16 Preparing for Installation System Example 2 continued Electrical installation scheme Main PCB 120V...

Страница 17: ...17 5693 982 04Vitotronic 300 GW2B Installation and Service Preparing for Installation System Example 2 continued Main PCB LV connections...

Страница 18: ...A1 to close the downstream mixing valves 0d 1 Boiler group Temperature sensor T1 Therm Control affects the mixing valves of downstream heating circuits factory set condition Wiring diagram Closing mi...

Страница 19: ...stem Example 3 Single boiler system Boiler with shunt pump and 3 way mixing valve for return temperature control Hydraulic installation scheme Note This scheme is a basic example without shut off devi...

Страница 20: ...Contact temperature sensor or Immersion temperature sensor rR ON OFF switch on site 9 DHW tank qP DHW tank temperature sensor STS qQ DHW pump UPSB qW DHW recirculation pump ZP qE Heating circuit 2 qT...

Страница 21: ...10V Specification of the set boiler water temperature eW 3 digital inputs External heating program changeover separately adjustable for heating circuits 1 to 3 External demand External blocking with...

Страница 22: ...Vitotronic 300 GW2B Installation and Service 5693 982 04 22 Preparing for Installation System Example 3 continued Electrical installation scheme Main PCB 120V...

Страница 23: ...23 5693 982 04Vitotronic 300 GW2B Installation and Service Preparing for Installation System Example 3 continued Main PCB LV connections...

Страница 24: ...4 24 Preparing for Installation System Example 3 continued Mixing valve extension PCB Required code 0C 1 Boiler group Constant return temperature control 4E 1 General group Connection plug gS A1 motor...

Страница 25: ...Preparing for Installation System Example 4 Single boiler system with Vitocrossal Hydraulic installation scheme Note This scheme is a basic example without shut off devices or safety equipment This d...

Страница 26: ...Heating circuit pump M2 Mixing valve extension kit qQ Supply temperature sensor M2 as contact temperature sensor and qE Mixing valve motor M2 or Supply temperature sensor M2 as qQ Contact temperature...

Страница 27: ...ater temperature eW 3 digital inputs External heating program changeover separately adjustable for heating circuits 1 to 3 External demand External blocking with fault message input Fault message inpu...

Страница 28: ...Vitotronic 300 GW2B Installation and Service 5693 982 04 28 Preparing for Installation System Example 4 continued Electrical installation scheme Main PCB 120V...

Страница 29: ...29 5693 982 04Vitotronic 300 GW2B Installation and Service Preparing for Installation System Example 4 continued Main PCB LV connections...

Страница 30: ...ut Therm Control temperature sensor System Extension Rated current 2 A If the circulation pump power consumption is above 2 A use a contactor relay Required code Group Function 33 3 1 General Function...

Страница 31: ...mounting surface with four fasteners 2 Fasten the junction box to the backplate with two fasteners 3 Install the control rear section to the junction box housing Hook the control to the backplate tab...

Страница 32: ...erface cover to the control cover 3 Release the stay bar and lock in position 4 Insert the plug from the programming unit to the control Note Route the ribbon cable through retainer A 5 Return the sta...

Страница 33: ...e Control Unit Installation 1 Remove the junction box cover screws and remove the cover 2 Remove the front housing screws 3 Swing up the front part of the control housing 4 Position the stay bar so th...

Страница 34: ...with VD2 and VD2A accessory for CT3 aJB Return temperature sensor T2 accessory or Temperature sensor primary store system optional accessory not used aVD External hook up aVG KM BUS participant acces...

Страница 35: ...300 GW2B Installation and Service Overview of Electrical Connections continued Legend A Vitotronic 300 GW2B B Junction box C Burner motor power supply refer to page 53 f Vitotronic 300 GW2B power supp...

Страница 36: ...shared between all 120V outputs Legend A 120V pump output B To the Vitotronic control unit C Junction box Available pump connections s M1 A1 Heat circuit pump switching contact shunt pump sL Boiler p...

Страница 37: ...estrain cables with zip tie to cable lead Inserting the Boiler Coding Card Only use the boiler coding card supplied with the boiler see table in chapter Components Insert the boiler coding card into s...

Страница 38: ...mit until the slot points to the desired temperature 3 Re fit the fuse box WARNING Disconnect power to the control and burner A B Legend A LON communication module accessory B Vitotronic 300 GW2B Non...

Страница 39: ...tion Sequence Legend Outside temperature sensor Boiler temperature sensor A DHW tank temperature sensor 1 B DHW tank temperature sensor 2 for primary store system optional accessory not used aJA Therm...

Страница 40: ...power supply to the control contains overcurrent protection with a minimum rating of 15A disconnect 2 Connect power supply wire to the connection f terminals 11 N and G on the DIN rail inside the junc...

Страница 41: ...ied C Pump D Power supply w disconnect and protection Contactor specification 120VAC 1A Legend A DIN rail B Contactor relay field supplied C Pump D Power supply w disconnect and protection Contactor s...

Страница 42: ...cket gS on the control 4 Fasten cable with tie 5 Connect black wire of the adaptor to terminals 8 9 or 10 on the Din rail 6 Connect valve actuator wires to the adaptor terminals Legend A 24V Mixing Va...

Страница 43: ...rconnection details 1 Remove jumper between terminals 12 and 15 2 Make connection as shown in diagram Legend aBH Power supply for accessories aB Connection for external equipment A Low water cut off t...

Страница 44: ...2 Connect dry contact Controlled switch off takes place when the contact is opened External Burner Blocking 150 Remove jumper from DIN terminals 16 and 17 Note Connect only safety shutdown equipment d...

Страница 45: ...Max pump current 2 FLA Mandatory Coding Address Changes 0C 5 Modulating isolation valve independant of boiler water temperature 0d 2 Switching contact 4A 1 17A Sensor installed 4b 1 17B Sensor instal...

Страница 46: ...Connection Note Live contacts lead to short circuits or phase failure The external connection must be floating Codes Plug aVH Extension EA1 No code required Set 5d 5E or 5F in the General group to 2...

Страница 47: ...ter temperature Installation Sequence Connection Note Live contacts lead to short circuits or phase failure The external connection must be floating Codes Plug aVD Extension EA1 Set coding address 99...

Страница 48: ...ating circuits via coding address 99 in the General group Note Live contacts lead to short circuits or phase failure The external connection must be floating Connection at plug aVD External Changeover...

Страница 49: ...re DHW heating in accordance with coding address 64 in the DHW group Codes Plug aVD Extension EA1 Via coding address 91 in the General group the function can be assigned to the heating circuits Set 5d...

Страница 50: ...DIN Rail inside connection enclosure refer to installation manual of Combustion Air Device Adaptor 3 Remove jumper between terminals 16 and 17 4 Make connection as shown in the diagram Wire BK2 must...

Страница 51: ...urner and boiler control 2 Connect plugs fA and plug l to respective counter plugs in boiler control unit 3 Connect the 7 pole plug fA and the 3 pole plug l to the burner Terminal codes 1 2 3 Control...

Страница 52: ...llow the burner manufacturer s connection drawings for Viessmann controls Note Write the terminal numbers or markings on the drawing for future reference For burner without plug in connection The burn...

Страница 53: ...disconnect 2 Connect power supply wire to the Connection f terminals 11 N and G on the DIN rail inside the connection enclosure Burner Connection Motor Power Supply Supply power must be sufficient to...

Страница 54: ...r motor power supply connection For burners with 240VAC 1PH power supply and connection in conduit See burner manual for correct fuse and wire gauge sizing and specific connections for Viessmann contr...

Страница 55: ...ect fuse and wire gauge sizing and specific connections for Viessmann controls 1 Disconnect power to burner and boiler control 2 Connect 3PH power to the terminals 21 22 23 and 24 on the DIN rail insi...

Страница 56: ...water temperature has dropped approx 15 to 20 K below the selected safety temperature 4 Reset the high limit safety cut out by pressing reset button Commissioning Changing the Language Setting the Da...

Страница 57: ...ct 25 Note Values up to and including 199 kW can be entered directly 09 Hundreds of the maximum burner output Example Max burner output 225 kW select 2 0A Ratio of output base load to maximum burner o...

Страница 58: ...o maximum burner output in percent Example Base load output 72 kW Max burner output 225 kW 72 kW 225 kW 100 32 05 Ratio of partial output at b of the servomotor runtime to maximum burner output in per...

Страница 59: ...ut Mixing valve closed enabled heating circuit with mixing valve M2 Htg circ pump HC3 ON Output for heating circuit pump enabled heating circuit with mixing valve M3 Mixing valve HC3 Open Output Mixin...

Страница 60: ...higher the boiler water or supply temperature The room temperature again depends on the boiler water or the supply temperature Adjusting Heating Curves Commissioning Slope Outside temperature in C Se...

Страница 61: ...egend A Boiler water temperature or supply temperature in F C B Outside temperature in F C C Set room temperature in F C D Heating circuit pump OFF E Heating circuit pump ON Changing the reduced set r...

Страница 62: ...tem with Vitotronic 200 H and Vitocom 100 LAN1 Set the LON participant numbers and further functions via code 2 see the following table Note In the same LON system the same participant number cannot b...

Страница 63: ...list with Delete list participant list is updated Note During the participant check the display for the relevant participant shows the participant no and Wink for approx 1 min Boiler control unit Vit...

Страница 64: ...a RJ45 plugs The Viessmann LON system always requires the cores 1 and 2 and the screen The cores are interchangeable The installation is therefore safe from pole errors Connection with Viessmann LON c...

Страница 65: ...check Service PIN Heating circuit 3 HC3 Coding level 2 Fault history Service functions Terminate service Reset data Service reset Service menu overview Press OK and simultaneously for approx 4 sec Pre...

Страница 66: ...ing data 1 Press OK and simultaneously for approx 4 sec 2 Diagnosis 3 Select required group e g General Scanning Operating Data In the brief scan you can scan temperatures software versions and connec...

Страница 67: ...ystem number Node address 0 0 8 SNVT config 0 Auto 1 Tool Software version Communic coproc Software version Neuron Chip Number of LON participants Heating circuit HC1 Heating circuit HC2 Heating circu...

Страница 68: ...et Note The selected service parameters for hours run and time interval restart at 0 Calling up acknowledged maintenance messages Extended menu 1 2 Service Fault Display Calling up acknowledged fault...

Страница 69: ...the outside temperature sensor RF close to the wireless base De register and then re register the outside temperature sensor Replace if necessary see separate installation and service instructions 30...

Страница 70: ...y pump ON Set DHW temperature set supply temperature Priority control is cancelled or With primary store system DHW tank heating is started and stopped by DHW tank temperature sensor 2 Short circuit D...

Страница 71: ...utput reduction mixing valve return temperature control Open Lead break temperature sensor aJA Check temperature sensor aJA see page 124 Without temperature sensor Set code 4A 0 in the General group 7...

Страница 72: ...ck sensor at the solar control unit see separate installation and service instructions 98 Control mode Lead break temperature sensor Connection at the solar control module Check temperature sensor see...

Страница 73: ...ernal safety equipment Check safety equipment and reset if required A1 Boiler cools down Fault safety equipment at X3 of plug in adaptor 2 for external safety equipment Check safety equipment and rese...

Страница 74: ...gas temperature sensor see page 125 Without flue gas temperature sensor Set code 1F 0 in the Boiler group bA Mixing valve Closed Communication error PCB extension for heating circuits 2 and 3 with mix...

Страница 75: ...ck the system water level of the system reset low water indicator C9 Boiler cools down Fault maximum pressure limiter at X3 of plug in adaptor 1 for external safety equipment Check system pressure res...

Страница 76: ...t Remove fault at appliance concerned d8 Control mode Input DE3 at extension EA1 reports a fault Remove fault at appliance concerned dA Control mode without room influence Short circuit room temperatu...

Страница 77: ...l be regulated subject to the respective boiler Function Description Brief description H The boiler water temperature is regulated by starting and stopping the burner or through modulation H The set b...

Страница 78: ...heat demand high heat demand Time ON OFF set Burner low heat demand average heat demand high heat demand Time ON OFF set Burner ERB80 function Code 04 2 Subject to heat demand values between 6 and 20...

Страница 79: ...flow rate in the startup phase e g after a weekend shutdown must be able to be reduced by at least 50 H Also affects the heating circuits of a Vitotronic 200 H installed downstream Raising the return...

Страница 80: ...t be controlled e g older heating systems or commercial nurseries Function Temperature sensors T1 and T2 capture the return temperature at different test points The shunt pump is started via temperatu...

Страница 81: ...res Activating party mode Changeover from central heating with reduced temp to central heating with standard temp Start optimization coding address b7 in the Heating circuit group Quick heat up will s...

Страница 82: ...economy function coding address A7 in the Heating circuit group Heating circuit pump logic economy mode The heating circuit pump is switched off set supply temperature set to 32 F 0 C if the outside...

Страница 83: ...tial temperature 8 K E Lower boiler water temperature defaulted by the boiler coding card Supply temperature control Raising the reduced room temperature During operation with reduced room temperature...

Страница 84: ...xing valve motor receives the signal Mixing valve closed The signal duration lengthens with an increasing control differential The duration of pauses reduces with an increasing control differential Fu...

Страница 85: ...mp can be adjusted individually for each heating circuit Function Description Brief description H The DHW tank temperature control is a constant temperature control This is the result of starting and...

Страница 86: ...ystems Set the following codes 55 3 in the DHW group 4C 1 4E 2 in the General group System with solar control unit A third set DHW temperature can be specified via coding address 67 in the DHW group T...

Страница 87: ...if a lot of hot water is drawn off The DHW tank heating will be switched off early if no hot water is drawn off DHW tank goes cold H Set value 2 5 K adjustable via coding address 59 or H Actual DHW te...

Страница 88: ...want to reset all codes to their factory set condition Select Standard setting in Coding level 1 Note This also resets codes on coding level 2 Code 1 Note H The codes are displayed as plain text H Co...

Страница 89: ...1 heating circuit 1 One heating circuit with mixing valve M2 heating circuit 2 without DHW heating automatic recognition 6 One heating circuit A1 heating circuit 1 One heating circuit with mixing valv...

Страница 90: ...99 1 boiler control unit 10 97 Vitotronic 200 H 98 Vitogate 99 Vitocom Note Each number must only be assigned once Detached house apartment building 7F 1 Detached house 7F 0 Apartment building Separa...

Страница 91: ...is displayed Burner service in 100 hours 21 0 No service interval hours run selected 21 1 to 21 100 The number of hours run before the burner should be serviced is adjustable from 100 to 10 000 h 1 s...

Страница 92: ...circuit pump is reduced if the actual DHW temperature is 5 K below the maximum DHW tank temperature 0A 0 Stagnation time reduction is disabled 0A 1 to 0A 40 Value for stagnation time reduction is adj...

Страница 93: ...circuit pump and mixing valve A2 0 Without DHW tank priority applicable to heating circuit pump and mixing valve A2 1 DHW tank priority applies only to the mixing valves A2 3 to A2 15 Modulating prior...

Страница 94: ...ction description on page 82 A9 0 Without pump idle time A9 1 to A9 15 With pump idle time adjustable from 1 to 15 1 short idle period 15 long idle period Weather compensated room temperature hook up...

Страница 95: ...he General group Heating program switches to Constant central heating with reduced room temperature or Standby mode subject to the settings of the set reduced room temperature d5 1 The heating program...

Страница 96: ...limit adjustable from 50 to 76 F 10 to 60 C F8 61 Function disabled End temperature raising F9 14 Temperature limit for raising the reduced set room temperature 7 F 14 C see example on page 83 F9 10...

Страница 97: ...you want to reset all codes to their factory set condition Select Standard setting in Coding level 2 Note This also resets codes from coding level 1 Code 2 Note H In coding level 2 all codes are acce...

Страница 98: ...ing valve M2 heating circuit 2 without DHW heating automatic recognition 6 One heating circuit without mixing valve A1 heating circuit 1 One heating circuit with mixing valve M2 heating circuit 2 with...

Страница 99: ...or external safety equipment 30 1 With plug in adaptor 1 for external safety equipment automatic recognition 31 1 Without plug in adaptor 2 for external safety equipment 31 1 With plug in adaptor 2 fo...

Страница 100: ...tic recognition 54 2 With Vitosolic 200 automatic recognition 54 3 With solar control module type SM1 without auxiliary function automatic recognition 54 4 With solar control module type SM1 with auxi...

Страница 101: ...l blocking with fault message 5F 5 Fault message input 5F 6 Brief operation DHW recirculation pump push button function Setting of runtime for DHW recirculation pump in coding address 12 in the Genera...

Страница 102: ...DHW heating possible 80 6 A fault message is displayed if a fault occurs for at least 30 sec 80 0 Immediate fault message 80 2 to 80 199 The minimum fault duration until a fault message is issued is...

Страница 103: ...ating circuits Heating circuit without mixing valve A1 heating circuit 1 91 2 Heating circuit with mixing valve M2 heating circuit 2 91 3 Heating circuits without mixing valve A1 heating circuit 1 and...

Страница 104: ...ing external Mixing valve closed see page 55 99 1 No function 99 2 External Mixing valve closed Heating circuit with mixing valve M2 heating circuit 2 99 3 No function 99 4 External Mixing valve close...

Страница 105: ...with mixing valve M2 heating circuit 2 and M3 heating circuit 3 9A 7 No function 9b 70 Set supply temperature for external demand 158 F 70 C 9b 0 to 9b 127 Set value adjustable from 32 to 261 F 0 to...

Страница 106: ...ondition specified by the boiler coding card 05 0 Linear burner curve 05 1 to 05 99 Non linear burner curve PT Pmax 100 PT in kW Partial output at g of the servomotor runtime Pmax in kW Maximum output...

Страница 107: ...urner start Factory set condition specified by the boiler coding card 16 0 to 16 15 Offset adjustable from 0 to 15 K 1A Start optimization in min Factory set condition specified by the boiler coding c...

Страница 108: ...arried out 26 0 Burner fuel consumption stage 1 No count if 26 0 and 27 0 are programmed 26 1 to 26 99 Input of 0 1 to 9 9 1 step 0 1 L h or gallons h Note Values of coding addresses 26 and 27 are add...

Страница 109: ...highest system supply temperature demand Scan of the temperature in the Diagnosis menu General Common dem temp see page 81 5A 1 For DHW heating The set supply temperature is determined by the DHW tan...

Страница 110: ...y boiler specific parameters Observe the setting of coding address 56 68 8 With 2 DHW tank temperature sensors code 55 2 DHW tank heating stop point at set value x 0 8 68 2 to 68 10 Factor adjustable...

Страница 111: ...ture control between the collector temperature and actual DHW temperature is adjustable from 5 to 20 K 04 4 Controller amplification of the speed control 4 K 04 1 to 04 10 Controller amplification adj...

Страница 112: ...medium 0E 2 Calculation of solar yield with water as heat transfer medium never adjust as operation is only possible with Viessmann heat transfer medium 0E 0 Calculation of solar yield switched off 0F...

Страница 113: ...fferential for central heating backup is adjustable from 2 to 30 K 23 4 Stop temperature differential for central heating backup 4 K Switching output sS is switched off when the temperature at sensor...

Страница 114: ...5 0 to 25 100 Stop temperature for thermostat function is adjustable from 0 to 100 K 26 1 Priority for DHW tank 1 with alternate heating Only when setting code 20 8 26 0 Priority for DHW tank 1 withou...

Страница 115: ...e control A2 2 DHW tank priority applicable to heating circuit pump and mixing valve A2 0 Without DHW tank priority applicable to heating circuit pump and mixing valve A2 1 DHW tank priority applies o...

Страница 116: ...tion Possible change A6 36 Extended economy control disabled A6 5 to A6 35 Extended economy control enabled i e the burner and heating circuit pump will be stopped and the mixing valve closed at a var...

Страница 117: ...ture hook up b2 8 With remote control and for the heating circuit operation with room temperature hook up must be programmed 2 Room influence factor 8 b2 0 Without room influence b2 1 to b2 64 Room in...

Страница 118: ...temperature C5 1 to C5 127 Minimum limit adjustable from 34 to 261 F 1 to 127 C limited by boiler specific parameters C6 75 Electronic maximum supply temperature limit set to 167 F 75 C C6 10 to C6 12...

Страница 119: ...ings of coding addresses 5d 5E 5F in the General group as well as d5 and d8 in the Heating circuit group F2 0 No time limit 1 F2 1 to F2 12 Time limit adjustable from 1 to 12 h 1 F8 5 Temperature limi...

Страница 120: ...ns Legend A1 PCB extension for heating circuits 2 and 3 with mixing valve A2 PCB low voltage A3 PCB 120V A6 Programming unit A7 Optolink PCB emissions test switch A8 PCB A9 Boiler Coding card A10 LON...

Страница 121: ...circuit pump on site f Power supply 120V 60 Hz fA Oil gas burners g Output for multiple fault messages gS Motor for 3 way mixing valve return temperature control or Motor for 3 way mixing valve primar...

Страница 122: ...mary store system aJA Therm control temperature sensor or Return temperature sensor T1 aJB Return temperature sensor T2 or Temperature sensor primary store system Optional accessory not used aG Flue g...

Страница 123: ...vice Connection and Wiring Diagram Type GW2B continued Designs Legend Supply temperature sensors s Heating circuit pumps f Power supply PCB extension for heating circuits 2 and 3 with mixing valve gS...

Страница 124: ...perature sensor in the mixing valve extension kit is a contact temperature sensor H The room temperature sensor is connected at terminals 3 and 4 in the Vitotrol 300A Sensors Installation and service...

Страница 125: ...Depending on the result replace the lead or the outside temperature sensor Outside temperature sensor When an entered limit in the Vitotronic 300 is reached see coding address 1F in Boiler group a se...

Страница 126: ...ull 3 PIN plug A in the mixing valve motor and reinsert turned through 180 2 Check the rotational direction Mixing valve Open Mixing valve Closed Changing the rotational direction if required Componen...

Страница 127: ...essage input External demand with minimum boiler water temperature Fault message input Brief operation of the DHW recirculation pump When connecting external contacts observe the requirements of safet...

Страница 128: ...upply plug f 3 pieces 0105 Plug ab 0106 Plug g 3 pieces 0108 Plugs aVD aVG aVH 3 pole 0109 Burner plugs fA l aBA and a A Ordering parts The following information is required H Serial no see type plate...

Страница 129: ...129 5693 982 04Vitotronic 300 GW2B Installation and Service Type GW2B continued Parts Lists...

Страница 130: ...relay output breaking capacity at 120V s Heating circuit pump or Primary pump primary store system or Circulation pump flue gas water heat exchanger or Switching output 2 A 3 sA Circulation pump for...

Страница 131: ...131 5693 982 04Vitotronic 300 GW2B Installation and Service...

Страница 132: ...Technical information subject to change without notice Printed on environmentally friendly recycled and recyclable paper 5693 982 04 Vitotronic 300 GW2B Installation and Service...

Отзывы: