![Viessmann VITOTRONIC 300 GW2B Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/viessmann/vitotronic-300-gw2b/vitotronic-300-gw2b_installation-and-service-instructions-manual_1017725042.webp)
Vitotronic 300, GW2B Installation and Service
5693 982 - 04
42
Connecting Actuators
Available connections
gS
A1 Motor for 3-way mixing valve, primary store system
gS
M2 For heating circuit 2
gS
M3 For heating circuit 3
Rated voltage:
120V~
Rated current Max.:
0.1A~
Motor runtime for
3-way mixing valve:
10 to 255 sec, adjustable via
coding
addresses
“6A” in
the”DHW”group, “C3” in the HC2
group and “C3” in the HC3 group.
1. Disconnect power to control.
2. Install 120V or 24V valve adaptor on DIN rail inside
connection
enclosure.
3. Insert the plug
gS
into socket
gS
on the control.
4. Fasten cable with tie.
5. Connect black wire of the adaptor to terminals 8,9 or
10 on the Din rail.
6. Connect valve actuator wires to the adaptor terminals
Legend
A
24V Mixing Valve Adaptor
B
DIN Rail (in junction box)
C
24V Valve Actuator
D
Valve
Legend
A
120V Mixing Valve Adaptor
B
DIN Rail (in junction box)
C
24V Valve Actuator
D
Valve
120V Valve Adaptor
Rated voltage:
120VAC
Rated current:
max. 0.1 FLA
Recommended connection wire size: AWG 14
24V Valve Adaptor
Rated voltage:
24VAC
Rated current:
max. 0.15 FLA
Recommended connection wire size: AWG 14
Operating time:
5 to 199 sec. selected via coding
address
“40”.
Refer to the mixing valve adaptor Installation
Instructions for additional information.
Installation Sequence