![Viessmann VITOTRONIC 300 GW2B Скачать руководство пользователя страница 63](http://html1.mh-extra.com/html/viessmann/vitotronic-300-gw2b/vitotronic-300-gw2b_installation-and-service-instructions-manual_1017725063.webp)
63
5693 982 - 04
Vitotronic 300, GW2B Installation and Service
Commissioning
Connecting the Control Unit to the LON
Carrying out a LON participant check at the Vitotronic
300-K
Communication with the system devices connected to the
fault manager is tested by means of a participant check.
Preconditions:
H
The control unit must be programmed as fault manager
(code “79:1”).
H
The LON participant no. must be programmed
in all control units
H
The LON participant list in the fault manager must
be up to date.
Performing the participant check:
1. Press
OK
and
simultaneously for approx. 4 sec.
2. “Service
functions”
3. “Participant
check”
4. Select participant (e.g. participant 10).
The participant check for the selected participant
is initiated.
H
Successfully tested participants are designated
with “
OK
”.
H
Unsuccessfully tested participants are designated
with
“Not OK”
.
Note:
To carry out a new participant check, create
a new participant list with “Delete list?”
(participant list is updated).
Note:
During the participant check, the display for the
relevant participant shows the participant no.
and “Wink” for approx. 1 min.
Boiler control unit
Vitotronic 200-H
Vitotronic 200-H
Vitocom LAN1
A
Terminal end resistor
Participant no. 1
Code “77:1”
Participant no. 10
Code “77:10”
Participant no. 11
Set code “77:11”.
Participant no. 99
Control unit is fault
manager
Code “79:1”
Control unit is not fault
manager
Code “79:0”.
Control unit is not fault
manager
Code “79:0”.
Device is fault manager.
Control unit transmits the
time
Code “7b:1”.
The control unit receives
the time
Set code “81:3”.
The control unit receives
the time
Set code “81:3”.
Device receives the time.
Control unit transmits
outside temperature
Set code “97:2”.
Control unit receives the
outside temperature
Set code “97:1”.
Control unit receives the
outside temperature
Set code “97:1”.
-
Viessmann system number
Code “98:1”
Viessmann system number
Code “98:1”
Viessmann system number
Code “98:1”
-
LON participant fault
monitoring
Code “9C:20”
LON participant fault
monitoring
Code “9C:20”
LON participant fault
monitoring
Code “9C:20”
-
A