Vitorond 200, VD2 Series 320 to 1080 Technical Data

Standard Equipment

Burner calibration

With 2-stage and fully modulating burners, ensure 

that the chimney is compatible with the lower flue gas 

temperatures associated with partial load conditions set 

on the burner.

2-Stage burner

When used with the or Vitotronic control, the following 

minimum heating outputs are applicable to protect the 

boiler:

 

- 60% of outputs stated in the Technical                         

Data table on page 5.

Fully modulating burner

The minimum boiler water temperature is:

 

- 140°F (60°C) with oil,

 

- 149°F (65°C) with natural gas.

Set the return temperature elevation system to maintain 

a minimum value of 127°F (53°C).

CAUTION

The Vitorond 200, VD2 boiler is not approved for side 

wall venting.

Chimney

For proper operation of the Vitorond 200, VD2 boiler, 

all products of combustion must be safely vented to 

the outdoors, while ensuring that flue gases do not cool 

prematurely.
It is critical that the chimney system be properly designed 

to handle the relatively cool flue gas temperatures 

produced by the Vitorond 200, VD2 boiler.
If the chimney system lacks sufficient insulation and/or 

the chimney diameter is too large, corrosive and damaging 

condensation will result due to flue gases cooling too 

quickly. If a calculated chimney diameter lies between two 

values, the larger diameter should be selected. 

The chimney connection length between the boiler vent 

pipe collar and the chimney must be installed with 

insulation. 
Vent pipe collar diameter does not automatically

indicate vent/chimney size. 
We recommend consulting a reputable chimney installer 

for advice in project-specific circumstances.
When installing the Vitorond 200, VD2 boiler, 

it is necessary to install a barometric draft regulator 

in the chimney/vent for proper operation of the boiler.
Install the barometric draft regulator within 5 to 7 ft. 

(1½ to 2 m) from the breeching outlet located at the 

rear of the boiler.

Venting

The Vitorond 200, VD2 boiler is approved as a Category I 

appliance and must be vented accordingly. 

System Design Considerations

Содержание VITOROND 200 Type VD2

Страница 1: ...pass hot water heating boiler 1255 to 4387 MBH 368 to 1285 kW Vitorond 200 Oil Gas fired boiler sectional cast iron design with Eutectoplex heat transfer surface in triple pass design for operation w...

Страница 2: ...mperature distribution further increase the level of operational reliability H Problem free transport into difficult to access boiler rooms due to sectional construction and low weight of individual s...

Страница 3: ...em up to 4 boilers 14 Vitotronic 100 type GC1B and LON module 14 Vitotronic 100 type GC1B and LON module 14 Vitotronic 300 K MW1B control panel 14 For single or multiple boiler installations 14 Custom...

Страница 4: ...exchanger surface constructed from homogeneous special gray cast iron Product may not be exactly as illustrated Third pass Vitotronic control intelligent and easy to install operate and service Burner...

Страница 5: ...Cast iron block dimensions Length in mm 57 1450 62 1580 67 1710 72 1840 77b 1970 82b 2100 88 2230 93 2360 98 2490 103 2620 108 2750 Width in mm 40b 1030 40b 1030 40b 1030 40b 1030 40b 1030 40b 1030 4...

Страница 6: ...3 160 353 160 353 160 353 160 353 160 353 160 Rear section with flue gas collar lbs kg 507 230 507 230 507 230 507 230 507 230 507 230 507 230 507 230 507 230 507 230 507 230 Cast iron heat exchanger...

Страница 7: ...563 1398 634 1552 704 1730 785 1907 865 2110 957 2394 1086 Boiler standby loss based on max heating input and hot water supply and return temps of 167 140 F 75 60 C 0 40 0 38 0 35 0 32 0 31 0 29 0 28...

Страница 8: ...be diameters of 7 to 11 in 180 to 280 mm the door insulation refractory material can be cut to the required size The blast tube must protrude from the thermal insulation on the boiler door Legend BD B...

Страница 9: ...sion tank SS Safety supply connection to pressure relief valve Low temperature protection Low temperature protection packages from Viessmann are required for Rondomat boilers A 30 Boiler Flow Package...

Страница 10: ...g the boiler pump normally supplied with the 100 Boiler Flow Package to verify that all pumps in the system operate correctly The responsibility for the distribution system design including all circul...

Страница 11: ...tle brush for heat exchanger cleaning IMPORTANT Minimum side clearance of 20 in 500 mm must be maintained for side mounted Vitotronic controls Recommended Minimum Clearances Boiler model VD2 320 VD2 3...

Страница 12: ...review the system design if more balancing valves are required to properly balance the system Viessmann can supply TA Victaulic balancing valves upon request The balancing should be carried out by a c...

Страница 13: ...fired 149 F 65 C min return water temperature 127 F 53 C The Viessmann or Vitotronic control system Setback operation Minimum boiler water temperature Oil fired 122 F 50 C Gas fired 140 F 60 C For mu...

Страница 14: ...ure in conjunction with an external control unit BMS H with Vitocontrol control panel Vitotronic 100 GC1 GC1B and LON module for modulating boiler water temperature for each boiler of the multi boiler...

Страница 15: ...s critical that the chimney system be properly designed to handle the relatively cool flue gas temperatures produced by the Vitorond 200 VD2 boiler If the chimney system lacks sufficient insulation an...

Страница 16: ...sion caused by flue gas condensation due to low boiler water and or return water temperatures Operation with contaminated fill and supplementary feed water System layout The boiler water temperature l...

Страница 17: ...burner start up procedures Burner manufacturer Weishaupt or Riello Burner Gas train approval Standard approvals are CSA for Canada and UL for U S IRI and FM approved equipment is also available please...

Страница 18: ...GL10 1 WM GL10 2 WM GL10 3 WM GL10 4 WM GL20 2 Riello Burners Boiler model VD2 320 380 440 500 560 630 700 780 860 950 1080 No 2 oil fired 2 stage Model RL28 2 RL38 2 RL50 2 RL50 2 RL100 2 No 2 oil f...

Страница 19: ...19 5285 428 03 Vitorond 200 VD2 Series 320 to 1080 Technical Data...

Страница 20: ...Technical information subject to change without notice Printed on environmentally friendly recycled and recyclable paper 5285 428 03 Vitorond 200 VD2 Series 320 to 1080 Technical Data...

Отзывы: