21
Adjusting the burner
Burner manufacturer’s details
Adjust the maximum fuel oil or gas
throughput of the burner to the rated
boiler output.
Permissible flow temperature 110 °C
Boiler
size
*2
Rated output
Resistance on flue gas side
HEL
Gas
HEL
*3
Gas
MW
MW
Pa
mbar
Pa
mbar
1
7.75
8.00
1020
10.2
1130
11.3
2
8.55
10.00
900
9.0
1180
11.8
3
10.12
12.00
990
9.9
1570
15.7
4
11.78
14.20
850
8.5
1420
14.2
5
13.43
16.50
880
8.8
1540
15.4
6
15.09
20.00
920
9.2
1880
18.8
Permissible flow temperature 120 °C
Boiler
size
*2
Rated output
Resistance on flue gas side
HEL
Gas
HEL
*3
Gas
MW
MW
Pa
mbar
Pa
mbar
1
7.75
8.00
1020
10.2
1130
11.3
2
8.55
10.00
900
9.0
1180
11.8
3
10.12
12.00
990
9.9
1570
15.7
4
11.78
14.20
850
8.5
1420
14.2
5
12.88
16.50
800
8.0
1540
15.4
6
12.88
16.74
650
6.5
1300
13.0
To protect the system against dew point
corrosion, the full load must be set to the
rated boiler output and must not be
switched off during the summer months
(full load at constant standby).
The minimum boiler water temperature
is 70 ºC. Adjust the return temperature
raising facility to a minimum temperature
of 50 ºC (operation with oil) or to 55 ºC
(operation with gas).
*2
The last digit of the part number indicates the boiler size.
*3
With a maximum permissible combustion output
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5727 529 GB
Service