32
Vitodens 222-F, B2TB
Application 3 Operational Setup Instructions
1.
Using Optional DE Connection- Using this connection
puts boiler in standby mode when there is no call for heat
from the system.
2.
Not using Optional DE Connection - The P1 circulator will
start/stop based on the low loss header temperature or
warm weather shutdown.
3.
The coding parameters described above are modified
in level 2 coding.
Step1
:To access this coding you must hold the "OK"
key and "ext. Menu" key together for 5 seconds. This
gives access to the service level.
Step 2
: Hold the "OK" key and "Return" key for 5
seconds. This gives access to level 2 coding
Notes/Comments
If zoning with pumps is your thing, then consider this application for your next install. In this system you have
a Vitodens 222-F, and a four zone single temperature system. Upon a call for heat from the thermostat, the
associated zone pump is energized by the multi zone control. Once the boiler detects a drop in temperature
at the low loss header, it is taken out of standby mode until the call for heat is satisfied. This is a very simple
control solution for single temperature applications. To setup this boiler for this application you will need to
complete the following:
Type/Option
Step#
Description
Parameter
Set to:
Setup
Location
Without the DE Contact
1
Setup HC1 Outdoor Reset Curve
Set in heating
sub menu
2
Set DHW Temperature
3
Configure P1 to shut down once low loss
header has reached its setpoint temperature
51:
:01
Set in Level 2 Coding
OR
Using the optional DE
Connection in
the boiler:
1
Setup HC1 Outdoor Reset Curve
Set in heating
sub menu
2
Set DHW Temperature
3
Configure P1 to operate upon a call for heat
Set in Level 2
Coding
Activates DE1 Contact
3A
:01
Initiates Changeover
D5
:01
Identifies changeover based on DE1 contact
D8
:01
Time limit for changeover
F2
:0
Temperature Limit for disabling changeover
F8
-61
Adjust Daytime schedule
--:--
Set in heating
sub menu
Set Reduced room temperature
3ºC
Optional Adjustments
Set a Heating Schedule
(not required if DE contact is being used as a changeover)
Set in heating
sub menu
Set an Individual DHW Schedule
Содержание Vitodens 222-F B2TB
Страница 2: ......
Страница 4: ...IV ...
Страница 10: ...6 ...
Страница 14: ...10 Technical Data Vitodens 222 F B2TB 19 and 35 Technical Data ...
Страница 29: ...25 Application 1 Operational Setup continued Notes Comments ...
Страница 33: ...29 Application 2 Operational Setup continued Notes Comments ...
Страница 37: ...33 Application 3 Operational Setup continued Notes Comments ...
Страница 41: ...37 Application 4 Operational Setup continued Notes Comments ...
Страница 45: ...41 Application 5 Operational Setup continued Notes Comments ...
Страница 49: ...45 Application 6 Operational Setup continued Notes Comments ...
Страница 51: ...47 47 Global presence Local commitment ...