Control unit for weather-compensated mode with standard prog. unit
Adjusting heating curves
(cont.)
Maximum temperature limit
Heating circuit
without
mixer
Setting of coding addressĂ"06"
Setting range of the max. temp. of
"06:01"Ă=Ă40Ă
º
C to "06:15"Ă=Ă110Ă
º
C
(Change per step: 5ĂK)
AsĂdeliveredĂcondition:Ă"06:10"Ă=Ă85Ă
º
C.
Heating circuit
with
mixer
Setting of coding addressĂ"05"
Setting range of the max. temp. of
"05:00"Ă=Ă35Ă
º
C to "05:15"Ă=Ă110Ă
º
C
(Change per step: 5ĂK)
AsĂdeliveredĂcondition:Ă"05:08"Ă=Ă75Ă
º
C.
5692Ă485
G
B
110
+20
-20
Boiler water temperature or flow temperature in ăC
º
Outside temperature in
º
C