Vitodens 200-W B2HA 88-150, 311- 530 Technical Data
11
5683 718 - 19
System Flow Rates
Boiler B2HA 112, 399 maximum flow rate; 38 GPM (8600 L/h)
Typical System Flow Rates
(continued)
Boiler B2HA 150, 530 maximum flow rate; 38 GPM (8600 L/h)
Model B2HA 112, 399
1 boiler
2 boilers
3 boilers
4 boilers
5 boilers
6 boilers
7 boilers
8 boilers
Output
(NG/LPG)
MBH
375
750
1125
1500
1875
2250
2625
3000
t for NG/LPG
20ºF rise GPM
(L/h)
37.5
(8500)
75
(17000)
112.5
(25600)
150
(34100)
187.5
(42600)
225
(51100)
262.5
(59600)
300
(68100)
25ºF rise GPM
(L/h)
30
(6800)
60
(13600)
90
(20400)
120
(27300)
150
(34100)
180
(40900)
210
(44700)
240
(54500)
30ºF rise GPM
(L/h)
25
(5700)
50
(11400)
75
(17000)
100
(22700)
125
(28400)
150
(34100)
175
(39700)
200
(45400)
35ºF rise GPM
(L/h)
21.4
(4900)
42.9
(9700)
64.3
(14600)
85.7
(19500)
107.1
(24300)
128.6
(29200)
150
(34100)
171.4
(38900)
40ºF rise GPM
(L/h)
18.8
(4300)
37.5
(8500)
56.3
(12800)
75
(17000)
93.8
(21300)
112.5
(25600)
131.3
(29800)
150
(34100)
Model B2HA 150, 530
1 boiler
2 boilers
3 boilers
4 boilers
5 boilers
6 boilers
7 boilers
8 boilers
Output
(NG/LPG)
MBH
495
990
1485
1980
2475
2970
3465
3960
t for NG/LPG
20ºF rise GPM
(L/h)
49.5
(11243)
99
(22487)
149
(33731)
198
(44974)
247.5
(56213)
297
(67461)
346.5
(78705)
396
(89949)
25ºF rise GPM
(L/h)
39.6
(8994)
79
(17990)
119
(26985)
158
(35979)
198
(44971)
237.6
(53969)
277
(62964)
317
(71959)
30ºF rise GPM
(L/h)
33
(7495)
66
(14991)
99
(22487)
132
(29983)
165
(37476)
198
(44974)
231
(52470)
264
(59966)
35ºF rise GPM
(L/h)
28
(6424)
57
(12850)
85
(19275)
113
(25700)
141.4
(32122)
170
(38549)
198
(44974)
226
(51399)
40ºF rise GPM
(L/h)
25
(5631)
50
(11244)
74
(16865)
99
(22487)
124
(28107)
148.5
(33731)
173
(39352)
198
(44974)