Vitodens 200-W B2HA 88-150, 311- 530 Technical Data
5683 718 - 19
10
Boiler B2HA 100, 352 maximum flow rate; 25 GPM (5700 L/h)
Model B2HA 100, 352
1 boiler
2 boilers
3 boilers
4 boilers
5 boilers
6 boilers
7 boilers
8 boilers
Output
(NG/LPG)
MBH
333
666
999
1332
1665
1998
2331
2664
t for NG/LPG
20ºF rise GPM
(L/h)
33.3
(7563)
66.6
(15128)
100
(22692)
133
(30255)
166.5
(37816)
200
(45383)
233
(52947)
266.4
(60510)
25ºF rise GPM
(L/h)
26.6
(6051)
53.3
(12102)
80
(18153)
106.6
(24204)
133
(30253)
160
(36307)
187
(42377)
213
(48409)
30ºF rise GPM
(L/h)
22.2
(5042)
44.4
(10085)
66.6
(15128)
89
(20170)
111
(25211)
133
(30255)
155.4
(35298)
178
(40341)
35ºF rise GPM
(L/h)
19
(4322)
38.1
(8644)
57
(12967)
76
(17289)
95
(21609)
114
(25933)
133
(30255)
152
(34578)
40ºF rise GPM
(L/h)
16.7
(3781.6)
33.3
(7564)
50
(11346)
66.6
(15128)
83
(18908)
100
(22692)
117
(26473)
133
(30255)
System Flow Rates
Typical System Flow Rates
Boiler B2HA 88, 311 maximum flow rate; 25 GPM (5700 L/h)
Model B2HA 88, 311
1 boiler
2 boilers
3 boilers
4 boilers
5 boilers
6 boilers
7 boilers
8 boilers
Output
(NG/LPG)
MBH
294
588
882
1176
1470
1764
2058
2352
t for NG/LPG
20ºF rise GPM
(L/h)
29.4
(6677)
58.8
(13355)
88.2
(20032)
117.6
(26709)
147.0
(33387)
176.4
(40064)
205.8
(46741)
235.2
(53419)
25ºF rise GPM
(L/h)
23.5
(5342)
47.0
(10684)
70.6
(16026)
94.1
(21367)
117.6
(26709)
141.1
(32051)
164.6
(37393)
188.2
(42735)
30ºF rise GPM
(L/h)
19.6
(4452)
39.2
(8903)
58.8
(13355)
78.4
(17806)
98.0
(22258)
117.6
(26709)
137.2
(31161)
156.8
(35612)
35ºF rise GPM
(L/h)
16.8
(3816)
33.6
(7631)
50.4
(11447)
67.2
(15262)
84.0
(19078)
100.8
(22894)
117.6
(26709)
134.4
(30525)
40ºF rise GPM
(L/h)
14.7
(3339)
29.4
(6677)
44.1
(10016)
58.8
(13355)
73.5
(16693)
88.2
(20032)
102.9
(23371)
117.6
(26709)