40
Display
Measure
Control unit issues a heat
demand
No
Increase set value and
ensure heat is drawn off
Yes
Fan starts
No
After approx. 1 min, fault
F9
Check the fan, fan con-
necting cables, fan power
supply and fan control
Yes
Ignition
No
Fault F4
Check the ignition module
connection
Yes
Gas train opens
No
Fault F4
Check the gas train
(230 V control voltage)
and gas supply pressure
Yes
Ionisation current builds
(above 2
µ
A)
Symbol
A
No
Fault F4
Check electrode adjust-
ment and gas line for air-
locks
Yes
Burner in operation
No
Shuts down below the set
boiler water temperature
and restarts immediately
Check the flue system for
tightness (flue gas recir-
culation); check the gas
flow pressure
Fault display
Fig. 32
In case of a fault, the display will show and the fault
code.
If flashes and
"R"
appears, the burner is locked out.
See page 42.
For an explanation of the fault codes, see the following
table.
Troubleshooting
Function sequence and possible faults
5697789
Diagnosis