99
5790 733 - 07
Vitocrossal 300 CA3 Series 2.5 to 6.0 Installation/Service
Service
1. Disconnect KM-BUS connector
avG
.
2. Undo 2 mounting screws. Torque when installing:
9 lb.in (1 Nm).
3. Lift the display and programming unit and pull off the
connector of the burner control unit connecting cable.
Remove the display and programming unit.
4. Pull the coding card from the burner control unit.
5. Insert new coding card.
6. For further steps, see chapter “Further assembly”
on page 117.
Note:
If fault code “
F b7
” is displayed, check the coding
card.
Refer to the Service Instructions.
Coding Card on Burner Control Unit
Display and Programming Unit of Burner Control Unit
1. Disconnect KM-BUS connector
avG
.
2. Undo 2 mounting screws. Torque when installing:
9 lb.in (1 Nm).
3. Lift the display and programming unit and pull off the
connector of the burner control unit connecting cable.
Remove the display and programming unit.
4. Install new display and programming unit in reverse order.
5. For further steps, see chapter “Further assembly”
on page 117.
NG coding card
Boiler Model
Burner model
Coding card part #
CA3 2.5 and 3.0
1.25 MMBTU
7863669
1.5 MMBTU
7863668
CA3 3.5 to 6.0
1.5 MMBTU
7866276
2.0 MMBTU
7862577