6
Product designation
5471970 GB - Subject to technical changes!!
Â
Document defects (e.g., with photos) and report
them to the manufacturer, specifying manufacturing
information and model designation. Pay attention to
loose parts, dents, and scratches as well as visible
loss of oil.
Â
Lift ceiling unit exclusively at the base of the
machine.
Â
Do not lift ceiling unit at the evaporator.
Â
Lift fan box exclusively at the circumferential
mounting plate.
Â
Ensure that the evaporator and condenser are not
damaged.
Â
Dispose of packaging material in an environmentally
compatible way according to local regulations.
6.2.3 Installation conditions
NOTE
Damage due to installation
outdoors!
f
Install ceiling units exclusively
in enclosed spaces..
Requirements for installation space
Â
Comply with ambient temperature from +10° C to
+42° C.
Â
Do not exceed humidity (non-condensing humidity)
of 85%.
Â
Maintain distance of 600 mm from all intake
openings in order to ensure the unimpeded intake of
the ceiling unit.
Â
Maintain distance of 750 mm from all exhaust
openings in order to ensure the unimpeded exhaust
of the ceiling unit.
Â
At least 100 mm gap from the top edge of the ceiling
unit to the bottom edge of the exiting ceiling.
Â
If distances cannot be maintained:
Have refrigeration specialist company properly
plan necessary air ducts.
Ensure airflow with appropriate measures
(e.g., air baffles, additional fans).
Â
Purge generated heat from the installation room.
Â
Avoid direct heat radiation.
Â
Avoid the ingress of warm, moist air into the cold
room
Â
Exclude installation in areas with magnetic
interference pulses that have an impact on the
functioning of the ceiling unit.
Â
Exclude installation in an explosive environment.
5 Product designation
Standard refrigeration units: CMC 0700, CMC 0900,
CMC 1300, CMC 1900, CMC 3300, CMC 4200
Freezer units: CMF 0800, CMF 1100,
CMF 1300, CMF 1700, CMF 2900, CMF 4100
Refrigeration capacity is specified at full 100W.
The abbreviations in the product designations stand for:
CM = Ceiling Monobloc
C = Cooler
F = Freezer
6 Installation
6.1 Transport
Transport ceiling unit as follows:
Â
Transport exclusively in position of use.
Â
Do not tilt ceiling unit.
Â
Comply with symbols on the packaging.
Â
Lift and transport unit exclusively at the base of the
machine.
Â
Ensure that the evaporator and condenser are not
damaged.
6.2 Installation
6.2.1 Scope of delivery
The delivery includes:
Fan box with frame panels (variations depending
on the selected cell wall thickness)
Insulation cover
Machine part with remote control
L
Viessmann Kühlsysteme GmbH delivers the ceiling
unit ready to be plugged in, i.e., ready to operate with
power supply cable including plug
6.2.2 Unpacking
NOTE
Damage due to tilting the ceiling
unit!
f
Ensure that the ceiling unit is not
tilted.
Before and during the unpacking:
Â
Comply with the safety and environmental
regulations at the installation site.
Â
Check ceiling unit for transport damages with a
visual inspection.
Содержание Tecto Refrigo CMC1
Страница 2: ...2 5471970 GB Subject to technical changes...
Страница 24: ...24 Dimensional drawings 5471970 GB Subject to technical changes 19 2 Size 2...
Страница 25: ...25 Dimensional drawings 5471970 GB Subject to technical changes 19 3 Size 3...
Страница 27: ...27 Drawings for ceiling cutout and drill holes 5471970 GB Subject to technical changes 20 3 Size 3 WS...