Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory setting
Change to
Description
Page
ARR
1
System
43
ROSA
0000
5
ROSA number
60
LOAD1 >
Loading 1
DT1O
6.0 K [12.0 °Ra]
Switch-on temperature difference 1
44
DT1F
4.0 K [8.0 °Ra]
Switch-off temperature difference 1
44
DT1S
10.0 K [20.0 °Ra]
Set temperature difference 1
44
RIS1
2 K [4 °Ra]
Rise 1
44
S1MAX
60 °C [140 °F]
Tank maximum limitation 1
44
SMXS1
2
Sensor tank max 1
44
LOAD2 >
Loading 2
DT2O
6.0 K [12.0 °Ra]
Switch-on temperature difference 2
44
DT2F
4.0 K [8.0 °Ra]
Switch-off temperature difference 2
44
DT2S
10.0 K [20.0 °Ra]
Set temperature difference 2
44
RIS2
2 K [4 °Ra]
Rise 2
44
S2MAX
60 °C [140 °F]
Tank maximum limitation 2
44
SMXS2
4
Sensor tank max 2
44
LST2
ON
Loading tank 2
45
COL >
Collector
CEM
130 °C [270 °F]
Collector emergency temperature
46
OCCO*
OFF
Collector cooling option
46
CMAX
110 °C [230 °F]
Collector maximum temperature
46
OCMN
OFF
Collector minimum limitation option
46
CMIN
10.0 °C [50.0 °F]
Minimum collector temperature
46
OTCO
OFF
Evacuated evacuated tube collector function option
46
TCST
07:00
Evacuated tube collector starting time
47
TCEN
19:00
Evacuated tube collector ending time
47
TCRU
30 s
Evacuated tube collector runtime
47
TCIN
30 min
Evacuated tube collector standstill interval
47
OCFR
OFF
Collector frost protection option
47
CFR O
4.0 °C [40.0 °F]
Antifreeze temperature collector on
47
CFR F
5.0 °C [42.0 °F]
Antifreeze temperature collector off
48
FRPST
1
Antifreeze tank selection
48
LLOGI >
Loading logic
LOGIC
PRIO
Priority logic
48