40
en-US/C
A
9. Loading tank 2 and tank 3
Î
Switch on or off the “loading tank 2” / “loading
tank 3” option.
Note
“Loading tank 3” can only be adjusted if a
3-tank system or vertical tank loading has
been selected in the sub-channel ARR.
10. Pump control type:
Î
Adjust the type of pump control for PUMP1.
Carry out this adjustment for PUMP2, PUMP3
if needed.
8. Maximum tank temperature:
Î
Adjust the maximum tank temperature
In 3-tank systems, the adjustment has to be car-
ried out for S2MAX and S3MAX as well.
7. Valve logic:
Î
Adjust the valve variant of the 3-port valves
Note
The valve variant can only be adjusted in
systems with two 3-port valves (ARR 5,7,9).
Î
Complete the commissioning menu by
pressing button 5:
The controller is then ready for operation and nor-
mally the factory settings will give close to optimum
operation.
11. Minimum speed:
Î
Adjust the minimum speed of the pump PUMP1.
For systems with 3 pumps, the adjustments must
also be carried out for PUMP2, PUMP3
Note
The minimum speed can only be adjusted if
burst control (PULS) or speed control via
an adapter (ADAP) has been selected in the
sub-channel PUMP1,2,3.
12. Maximum speed:
Î
Adjust the maximum speed of the pump PUMP1.
For systems with 2 or 3 pumps, the adjustments
must also be made for PUMP2, PUMP3.
Note
The maximum speed can only be adjusted
if burst control (PULS) or speed control via
an adapter (ADAP) has been selected in the
sub-channel PUMP1,2,3.