61
Instantaneous heating water heater
Parameters for
Instantaneous heating water heater
Setting
"Electr booster heater"
Ó
"Enable instantaneous heating water heater 7900"
"1"
"Electr booster heater"
, if applicable
Ó
"Enable instant. heating water heater for central heating 7902"
"1"
"Electr booster heater"
Ó
"Output for instant. heating water heater at power-OFF 790A"
"1"
: 3 kW
"2"
: 6 kW
"3"
: 9 kW
"DHW"
, if applicable
Ó
"Enable electric heaters for DHW heating 6015"
"1"
External heat source
External heat source parameters
Setting
"External heat source"
Ó
"Enable external heat source 7B00"
"1"
With circulation pump for DHW reheating:
"External heat source"
Ó
"Enable booster heaters for DHW heating 6014"
"1"
"External heat source"
Ó
"Enable external heat source for DHW heating 7B0D"
"1"
Swimming pool water heating
Parameters for swimming pool heating
Setting
"System definition"
Ó
"External extension 7010"
"1"
or
"3"
"System definition"
Ó
"Swimming pool 7008"
"1"
Solar
Parameters for solar thermal system in conjunction with solar
control module, type SM1
Setting
"Solar"
Ó
"Type solar control unit 7A00"
"3"
"Solar"
Ó
Parameter C0xx
See installation and service instructions for
"solar control module, type SM1".
Cooling function
Cooling function parameters
Setting
"Cooling"
Ó
"Cooling function 7100"
"0"
No cooling
"1"
Natural cooling with NC-Box without mix-
er (accessory)
"2"
Natural cooling with NC-Box with mixer
(accessory)
"3"
"Active cooling"
"Cooling"
Ó
"Cooling circuit 7101"
"1"
Heating circuit A1/HC1
"2"
Heating circuit M2/HC2
"3"
Heating circuit M3/HC3
"4"
Separate cooling circuit SKK
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5549 984 GB