70
qR
Secondary circuit return temperature sensor
qT
Filter dryer
qZ
Only type WW 302.B125, WW 302.B155, WW 302.B200, WW 302.B250, WW 302.B300:
Second parallel filter dryer
qU
Condenser
qI
Evaporator
qO
Primary circuit return temperature sensor (heat pump brine outlet)
wP
Secondary circuit flow temperature sensor
wQ
Primary circuit flow temperature sensor (heat pump brine inlet)
wW
Flow switch
wE
Frost stat
wR
Temperature sensor for frost stat
wT
Sight glass, if installed
Draining the heat pump on the primary/secondary side
Drain the heat pump at the on-site drain valve (pri-
mary/secondary side).
Checking sensors
Sensor
Test element
Connection/installation
position
■
Outside temperature sensor (F0)
■
Flow temperature sensor, heating circuit M2/HC2 (F12)
■
Cooling circuit flow temperature sensor (direct heating circuit
A1/HC1 or separate cooling circuit SKK) (F14)
■
Room temperature sensors
10 kΩ (NTC)
See controller and sensor
PCB (see page 46)
■
Buffer temperature sensor (F4)
■
Cylinder temperature sensor (F6)
■
Flow/return temperature sensor, secondary circuit (F8/F9)
■
System flow temperature sensor (F13)
■
Boiler water temperature sensor, external heat generator
(F20)
10 kΩ (NTC)
All sensors in the heat pump refrigerant circuit
Temperature sensors, type NTC 10 kΩ
10
Temperature in °C
Resistance in kΩ 0.4
0.6
2
4
10
20
0.8
1
6
8
30
50
70
90 110
Fig.46
Temperature sensors, type Pt500A
420
400
440
460
480
500
520
540
560
580
600
-40 -30 -20 -10 0
10 20 30 40
Outside temperature in °C
Resistance
in Ω
Fig.47
Troubleshooting
Repairs
(cont.)
5549 984 GB
Service