![Viessmann H32E B300 Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/viessmann/h32e-b300/h32e-b300_installation-and-service-instructions-manual_1017777035.webp)
35
Vitovent 300-W
Type
H32S
B300
H32E
B300
H32S
B400
H32E
B400
Max. air flow rate
m
3
/h
300
300
400
400
Max. external pressure drop
at max. air flow rate
Pa
175
175
175
175
Factory setting of air flow rates
Background ventilation
m
3
/h
50
50
50
50
Reduced ventilation
m
3
/h
100
100
100
100
Nominal ventilation
m
3
/h
150
150
200
200
Intensive ventilation
m
3
/h
225
225
300
300
Setting ranges for air flow rates
Background ventilation
m
3
/h
0/50
0/50
0/50
0/50
Reduced ventilation
m
3
/h
50 to 300 50 to 300 50 to 400
50 to 400
Nominal ventilation
m
3
/h
50 to 300 50 to 300 50 to 400
50 to 400
Intensive ventilation
m
3
/h
50 to 300 50 to 300 50 to 400
50 to 400
Air intake temperature
Min.
°C
–
20
–
20
–
20
–
20
Max.
°C
35
35
35
35
Humidity
Max. relative room air humidity
%
70
70
70
70
Max. absolute extract air humidity
g/kg
12
12
12
12
Casing
Material
Sheet steel
Colour
White
Material of profiles for noise attenuation and thermal in-
sulation
EPS plastic
Dimensions
excluding connectors
Total length (depth)
mm
540
540
540
540
Total width
mm
677
677
677
677
Total height
mm
843
843
843
843
Total weight
kg
39
44
39
44
Number of
radial DC fans
With constant flow rate control, inlet on one side only,
with backward curved impeller vanes
2
2
2
2
Filter class
to EN 779
Outdoor air filter (delivered condition/accessories)
G4/F7
F7/
—
G4/F7
F7/
—
Extract air filter (delivered condition/accessories)
G4/G4
M5/
—
G4/G4
M5/
—
Heat recovery
Rate of temperature change to ErP
%
86
77
85
74
Rate of temperature change to EN 308:1997
%
Up to 90
78
Up to 93
78
Heat recovery level to DIBt
%
86
Up to
136
85 Up to 136
Heat recovery level to PHI
%
84
—
84
—
Material of countercurrent/enthalpy heat exchanger
PETG
PEM
PETG
PEM
Rate of humidity change
%
—
54
—
50
Specification
Specification
5816563
Appendix