Operating instructions
Setting air flow rates
Installation and service instructions for the "ven-
tilation programming unit, type LB1" or the heat
generator
Adjusting the air flow rates
B
C
A
D
Fig. 12
A
Supply air/extract air vent
B
Measuring funnel with defined cross-section for
determining the air speed
C
Impeller air speed meter
D
Checking at the floor outlet without measuring fun-
nel:
Where available, the test can also be carried out
with a suitable measuring funnel.
1.
■
Set ventilation level 2.
■
If installed,
disable
the monitoring of relative
humidity and CO
2
concentration.
–
Ventilation programming unit, type LB1/heat
pump control unit:
Set
"C1B0"
to
"0"
.
–
Control unit of wall mounted gas condensing
boiler:
Set
"B0"
to
"0"
.
Operating instructions
2.
With an impeller air speed meter, check the air
speed (or the air flow rate directly) at the supply air
and extract air vents. Observe the instructions of
the test equipment manufacturer.
Record actual values in the commissioning report.
Note
Use measuring funnel
B
for supply air and extract
air valves. This enables the entire air flow rate at
the annular gap of the supply air/extract air valve to
be captured.
The measuring funnel may not be suitable for
larger supply air and extract air apertures (e.g.
floor outlets). Take several measurements across
the area. Calculate the average value of the meas-
urements.
3.
Determine the deviation between the calculated
(from engineering plans) and actual air flow rates.
4.
Adjust the supply air/extract air vents in accord-
ance with the deviation.
Record the new aperture widths/annular gap in the
commissioning report.
5.
Repeat the air speed test. Check readjustment.
Record the new values in the commissioning
report.
6.
Fix the aperture width on the supply air/extract air
vent after the final adjustment (if necessary secure
with a locknut).