4.5 Settings Checklist
4.5 Settings Checklist
Tables for entering System Settings / Equipment
All functions, their default factory settings, as well as their alternatively possible settings are outlined in this table, Ensure functions which
have been altered are checked off accordingly.
Default factory setting
Alternative possibilities
Safety temperature high limit
” ”
H
Default setting of 248
ºF
/ 120
º
C
j
Adjusted to .........
ºF
, or .........
º
C
Adjustable high limit
” ”
H
Default setting of 167
ºF
/ 75
º
C
j
Adjusted to .........
ºF range
, or .........
º
C range
Electronic high temperature limit
H
Default setting of 261
ºF
/ 127
º
C
j
Adjusted to .........
ºF
, or .........
º
C
H
The boiler water temperature is displayed on the
control unit
j
The outdoor temperature is displayed on the
control unit
j
The boiler water temperatures of the three boilers (if three
installed) and the pump operating conditions
(Display
*1
: pump in operation)
Burner
H
2-Stage burner operation
H
The switching hysteresis for the burner is 7
ºF
/ 4
º
C
H
If the burner is operated on a modulating basis:
Operating time of actuating drive for the burner is in the
range:
20 to 40 seconds
H
On multi-boiler systems
2-stage burners:
The burner stages are switched on and off in cascade
H
Modulating burners:
The burners are switched on and off in cascade
H
Without
external switching contact for changing over from
staged to modulating operation of the burner
j
The burner is operated on a single-stage basis
j
The burner is operated on a modulating basis
j
The switching hysteresis matches itself automatically to the
boiler load; values are set between 11 and 22
ºF
/ 6 and 12
º
C;
the minimum operating time for the burner is four minutes
j
Operating time of the actuating drive for the burner
in the range:
j
1
5 to 10 seconds
in the range:
j
10 to 20 seconds
in the range:
j
40 to 80 seconds
j
The burner stages are switched on and off in parallel
j
The burner stages are switched on in cascade and switched off
in parallel
j
The burners are switched on in cascade and switched off in
parallel
j
With external switch contact for changing over from staged to
modulating operation of the burner
H
Without flue gas temperature sensor
j
With flue gas temperature sensor
H
With return temperature sensor (RLS)
j
Without return temperature sensor (RLS)
H
The minimum boiler water temperature limit is 68
ºF
/ 20
º
C
j
The minimum boiler water temperature limit is set to
..... ºF / ..... ºC
H
If system pump
is built-in:
The system pump is switched on
continuously
.
Exception:
The system pump is switched off for domestic
hot water heating with priority control.
133
j
The system pump is switched on
demand
.
Exceptions:
- The system pump is switched off for domestic hot water
heating with priority control despite a possible heat demand
for room heating.
- The system pump is switched on when there is a risk of
freezing, even if no heat is required for room heating.
- When the system is shut down for a long period, the
system pump is switched on for approx. five seconds
every 24 hours to prevent the pump from seizing up.
*1
SP = system pump, BP = boiler (shunt) pump, IP = individual boiler pump, DP = DHW tank pump