Coding in the delivered condition
Possible change
A9:7
With pump idle time:
Heating circuit pump
"Off" in case of set value
modification by changing
the operating mode or
changing the set room
temperature
A9:0
Without pump idle time
A9:1
to
A9:15
With pump idle time;
adjustable from 1 to 15
b0:0
With remote control:
Heating mode/reduced
operation: Weather-com-
pensated (change code
only for the heating circuit
with mixer)
b0:1
Heating mode: Weather-
compensated
Reduced mode: With room
temperature hook-up
b0:2
Heating mode: With room
temperature hook-up
Reduced mode: Weather-
compensated
b0:3
Heating mode/reduced
mode: With room tempera-
ture hook-up
b2:8
With remote control and
for the heating circuit,
operation with room tem-
perature hook-up must be
programmed: Room influ-
ence factor 8 (change
code only for heating cir-
cuit with mixer)
b2:0
Without room influence
b2:1
to
b2:64
Room influence factor
adjustable from 1 to 64
b5:0
With remote control: No
room temperature-
dependent heating circuit
pump logic function
(change code only for
heating circuit with
mixer)
b5:1
to
b5:8
Heating circuit pump logic
function, see the following
table:
Parameter
address b5:...
With heating circuit pump logic function:
Heating circuit pump "Off"
Heating circuit pump "On"
1
RT
actual
> RT
set
+ 5 K
RT
actual
< RT
set
+ 4 K
2
RT
actual
> RT
set
+ 4 K
RT
actual
< RT
set
+ 3 K
3
RT
actual
> RT
set
+ 3 K
RT
actual
< RT
set
+ 2 K
4
RT
actual
> RT
set
+ 2 K
RT
actual
< RT
set
+ 1 K
5
RT
actual
> RT
set
+ 1 K
RT
actual
< RT
set
Code 2
Heating circuit 1, heating circuit 2, heating…
(cont.)