104
Displayed
fault code
System characteris-
tics
Cause
Measures
F9
Burner in a fault
state
Fan speed too low
during burner start
Check fan, fan connecting
cables and power supply;
check fan control.
Press reset button
R
FA
Burner in a fault
state
Fan not at stand-
still
Check fan, fan connecting
cables and fan control.
Press reset button
R
FC
Burner in a fault
state
Gas train faulty,
faulty modulation
valve control or flue
gas path blocked
Check gas train. Check
flue system.
Press reset button
R
Fd
Burner in a fault
state
Fault, burner con-
trol unit
Check ignition electrodes
and connecting cables.
Check whether a strong
interference (EMC) field
exists near the appliance.
Press reset button
R
Replace control unit if
fault persists.
FE
Burner blocked or in a
fault state
Boiler coding card
or main PCB faulty
Press reset button
R
Replace boiler coding
card or control unit if the
fault persists.
FF
Burner blocked or in a
fault state
Internal fault or
reset button
R
blocked
Start the appliance again.
Replace the control unit if
the appliance will not
restart.
Troubleshooting
Fault codes
(cont.)
5692 860 GB