34
Troubleshooting
Diagnostics
(cont.)
Fault
code
display
System
characteristics
Cause
Remedy
36
The fan speed during
start−up or operation
stays outside its set
range longer than
5s; the speed for
ignition setting or
start output during
operation is not
achieved
Fan faulty, cables
faulty or broken
Check cables,
replace fan
37
Fan does not reach
set speed
Fan faulty, cables
faulty or short
circuited, fan blocked
by debris
Check cables,
replace fan, remove
debris
42
Burner control unit
remains in start−up
position, no start−up
in spite of heat
demand
JumperB
2 missing
or broken
Check jumperB
2
(see page40)
A
Burner control unit
in fault state
JumperB
3 missing
or broken
Check jumperB
3
(see page40)
L
Air pressure switch
shuts down during
operation
Flue gas backed up,
flue gas collector or
system contaminated
Remove flue gas
blockage, clean flue
gas collector and
flue system, if
necessary
Internal system errors
Internal system errors are created if a perfect program sequence can no
longer be guaranteed.
Fault code
display
Error in range
Cause
Remedy
01 and 02,
04 to 15,
70 to 79,
7A
Burner control unit
Internal system error
in burner control
unit
Replace burner
control unit
5692500GB
Содержание CU3
Страница 38: ...38 Burner Component summary 5692 500 GB M A B C D E L K H G F M H F N G O K ...
Страница 42: ...42 Parts list Parts list cont 5692 500 GB 201 205 213 1 212 1 202 208 209 210 A B C ...
Страница 43: ...43 Parts list Parts list cont 5692 500 GB 206 203 209 204 211 211 211 211 211 211 201 200 ...
Страница 45: ...45 Parts list Parts list cont 5692 500 GB 003 003 008 009 005 008 001 002 007 004 006 ...
Страница 47: ...47 Appendix Maint service Maint service Maint service Maint service 5692 500 GB ...
Страница 49: ...49 Appendix Maint service Maint service Maint service Maint service 5692 500 GB ...
Страница 51: ...51 Appendix Maint service Maint service Maint service Maint service 5692 500 GB ...