27
Troubleshooting
Setting the burner control unit parameters
DIP switch settings
The DIP switches at the back of the display and programming unit of the
burner control unit must be set to the rated burner output.
For displaying the selected parameter set, see below.
For confirming a newly adjusted parameter set (e.
g. after replacing the burner
control unit) see page28.
27kW
¢
parameter set10
35kW
¢
parameter set11
49kW
¢
parameter set12
66kW
¢
parameter set13
Displaying the selected parameter set
1.
Press keys
b
and
S
simultaneously. Under status, the
following is shown in the
display:"
1
".
2.
Press
S
, until the display
shows"
2
" under status. The two
digit display below service
indicates the selected parameter
set.
3.
Press keys
a
and
S
simultaneously; the operating
display will then be shown again.
5692500GB
ON
ON
ON
ON
Status
Service
Содержание CU3
Страница 38: ...38 Burner Component summary 5692 500 GB M A B C D E L K H G F M H F N G O K ...
Страница 42: ...42 Parts list Parts list cont 5692 500 GB 201 205 213 1 212 1 202 208 209 210 A B C ...
Страница 43: ...43 Parts list Parts list cont 5692 500 GB 206 203 209 204 211 211 211 211 211 211 201 200 ...
Страница 45: ...45 Parts list Parts list cont 5692 500 GB 003 003 008 009 005 008 001 002 007 004 006 ...
Страница 47: ...47 Appendix Maint service Maint service Maint service Maint service 5692 500 GB ...
Страница 49: ...49 Appendix Maint service Maint service Maint service Maint service 5692 500 GB ...
Страница 51: ...51 Appendix Maint service Maint service Maint service Maint service 5692 500 GB ...