Page 7 GB
4
Right reserved to make technical changes!
Seal the space between frame and cut-out with silicon.
and adhere with armaflex tape.
Mount the ceiling panel on the coldroom.
Lift the machine section of the refrigeration unit up to the
ceiling of the coldroom and position it on the cutout section
such that the insulating wall of the unit is approx 10mm over the
frame and the distance between frame and unit wall is about
50mm.
Do not lift the unit by the evaporator!
Carefully push the insulation cover over the evaporator and
connect it with the insulating wall of the unit using the excenter
locks.
The two lock holes on the cover must be closed with the
enclosed stoppers.
The cover and the unit wall should be approx 10mm over the
ceiling cut-out, such that any dripping defrosting water can run
off.
10mm