Mounting the burner
1.
16
18 Nm
2.
3.
Fig. 5
1.
Hook the burner onto the hinge bracket and secure
with the split pin.
!
Please note
Mechanical damage to delicate components
will impair the burner function.
Carefully insert the burner into the combus-
tion chamber. Do not damage the burner
gauze assembly, electrodes or insulation
block.
2.
Close the burner. Tighten the screws diagonally.
Torque: 18 Nm
3.
Check that the gap between the boiler front panel
and the hinge bracket is 16 mm
±
0.5 mm, so that
the boiler door closes tightly. Correct if necessary
using the 4 nuts.
Torque: 18 Nm
Danger
Leaks from the boiler door can result in poi-
soning through escaping flue gas.
Check the boiler door for leaks. For exam-
ple, use a dew point indicator, thermal imag-
ing or flue gas sensor.