Vitocrossal 200, CM2-400, -500 and -620 Technical Data
Technical Data
Specifications
Boiler Model
CM2
400
500
620
Input
MBH
1445
1800
2245
(kW)
(423)
(527)
(658)
Minimum Input NG
MBH
287
358
450
(kW)
(84)
(105)
(132)
Minimum Input LPG
MBH
351
440
545
(kW)
(103)
(129)
(160)
Output
*
1
MBH
(kW)
1372
(402)
1710
(501)
2132
(625)
Net AHRI rating
MBH
(kW)
1193
(350)
1487
(436)
1854
(543)
Combustion efficiency
*
1
%
95.1
95.1
95.1
Thermal efficiency
*
1
%
95.0
95.0
95.0
Overall length(e)
in.
89
b
95
5/
8
100
7/
8
(mm)
(2273)
(2429)
(2562)
Overall width (c)
in.
42
3/
8
42
3/
8
44
3/
8
(including insulation)
(mm)
(1078)
(1078)
(1128)
Overall height (a)
in.
65
5/
8
65
5/
8
68
c
(including control unit)
*
2
(mm)
(1666)
(1666)
(1748)
Concrete boiler base
Length
in.
46
5/
8
53
58
(mm)
(1185)
(1345)
(1475)
Width
in.
42.5
42.5
44.5
(mm)
(1245)
(1245)
(1295)
Thickness
in.
4
4
4
(mm)
(100)
(100)
(100)
Weight
Boiler body
lb
1136
1257
1488
(Kg)
(515)
(570)
(675)
Complete with the burner, control
lb
1495
1662
1929
and thermal insulation
(Kg)
(678)
(754)
(875)
Note:
For high altitude installations 5,000 to 10,000 ft. (1500 to 3000 m), the input will have an altitude de-ration of
15% for 5,000 ft. (1500 m) and 18% for 10,000 ft. (3000 m)
*
1
Tested to U.S. Standards ANSI Z21.13/CSA 4.9 and AHRI, BTS-2000 Testing Standard Method to determine the
efficiency of Commercial Heating Boilers.
*
2
Add 1
f
in. (40 mm) when using seismic mounts (optional accessory).