10
5773 596 v1.0
Vitocrossal 200, CM2-400, -500 and -620 Technical Data
Cylinder Burner
Specifications
Boiler Model CM2
400
500
620
Voltage
V
120
120
120
Frequency
Hz
60
60
60
Power consumption NG
at max. input
W
540
700
900
at min. input
W
54
60
60
Power consumption LPG
at max. input
W
467
590
700
at min. input
W
59
68
60
Version
modulating
Dimensions
Length
in. (mm)
38
5/8
(980)
38
5/8
(980)
41
¾
(1060)
Width
in. (mm)
26 (661)
26
5/8
(675)
26
5/8
(675)
Height
in. (mm)
21
a
(540)
20
5/8
(525)
24
b
(622)
Weight
Burner only
Burner package (with kits, flanges and
mounting hardware)
lb. (kg)
lb. (kg)
75 (34)
91 (41.3)
90 (41)
90 (41)
93 (42)
93 (42)
Min. gas supply pressure
Natural gas
“w.c.
4
4
4
Liquid propane gas
“w.c.
10
10
10
Max. gas supply pressure
Natural gas
“w.c.
14
14
14
Liquid propane gas
“w.c.
14
14
14
Gas connection
NPT
1
a
1
a
1
a
Specifications