106
Rated voltage
230 V
Rated frequency
50 Hz
Protection class
I
Permissible ambient temper-
ature
■
Operation
0 to +40 °C
■
Storage and transport
-20 to +65 °C
Backup fuse (power supply)
max. 16 A
Rated heating output range
P
cond
: T
F
/T
R
= 50/30
kW
16 - 80 32 - 120 32 - 160 48 - 200 48 - 240 64 - 280
64 - 318
P
n
: T
F
/T
R
= 80/60
kW
15 - 74 29 - 110 29 - 146 44 - 184 44 - 220 58 - 258
58 - 291
Rated heat input
kW
76
113
151
189
226
264
300
Product ID
CE-0085CR0391
Permiss. operating tempera-
ture
°C
95
Permiss. flow temperature
(= safety temperature)
°C
110
Max. permiss. operating pres-
sure
bar
6
MPa
0.6
Min. permiss. operating pres-
sure
*2
bar
1
MPa
0.1
Test pressure
bar
7.8
MPa
0.78
Boiler body dimensions
Length
mm
665
770
770
890
890
1004
1004
Width
mm
680
Height
mm
1650
Total dimensions
incl. casing,
boiler flow and return; excl. boil-
er flue connection
Length
mm
739
862
862
967
967
1085
1085
Width
mm
750
Height
mm
1650
Foundation dimensions
Length
mm
750
850
850
1000
1000
1100
1100
Width
mm
800
800
800
800
800
800
800
Height
mm
100
100
100
100
100
100
100
Weight
Overall unit weight
kg
238
295
295
340
340
385
385
Packed unit
kg
288
345
345
390
390
435
435
Boiler body
kg
183
230
230
265
265
300
300
Boiler body with transport pallet kg
210
260
260
295
295
330
330
Burner
kg
10
11
11
15
15
15
15
Water capacity
l
65
103
103
145
145
180
180
*2
The minimum operating pressure is essential for safe operation. It can be ensured with a minimum pressure switch (1 x per
system for multi boiler systems)
Specification
Vitocrossal specification
5839829