71
"Viessmann system number"
Setting
Explanations
1
98:1
Viessmann system number
In conjunction with monitoring several systems via
Vitocom 300
...
98:1 to
98:5
System number adjustable from 1 to 5
"Recognition, extension DAP1"
Setting
Explanations
Without
99:0
Never adjust
With
99:1
"Recognition, extension DAP2"
Setting
Explanations
Without
9A:0
Never adjust
With
9A:1
"Set flow temperature for external demand"
Setting
Explanations
70 °C
9B:70
... °C
9B:0 to
9B:127
Adjustable from 0 to 127 °C
Limited by boiler-specific parameters
"LON subscriber monitoring"
Setting
Explanations
20 min.
9C:20
If there is no response from a subscriber for 20 min,
the values specified in the control unit are used. Only
then will a fault message be issued.
... Min.
9C:2 to
9C:60
Adjustable from 2 to 60 min
"Differential temperature"
Setting
Explanations
8 K
9F:8
The differential temperature is the value by which the
common flow temperature should be higher than the
highest currently required flow temperature of the
heating circuits with mixer.
Only in connection with heating circuit with mixer M2
(heating circuit 2) and M3 (heating circuit 3)
... K
9F:0 to
9F:40
Adjustable from 0 to 40 K
Boiler
Note
Parameter values in
bold
are factory settings.
Parameter level 2
General
(cont.)
5789 302 GB
Parameter
Содержание B2TB
Страница 6: ...6 15 Keyword index 152 Index Index cont 5789 302 GB ...
Страница 12: ...12 1 4 2x 3 2 5 Fig 5 Installing the boiler Removing the front panels 5789 302 GB Installation ...
Страница 26: ...26 2 2x 4 1 5 3 Fig 19 Installing the boiler Fitting the front panels 5789 302 GB Installation ...
Страница 117: ...117 Parts lists Hydraulics 5789 302 GB Components ...
Страница 128: ...128 0008 0009 0004 0005 0006 0003 0002 0001 0007 Fig 75 Parts lists Miscellaneous 5789 302 GB Components ...
Страница 154: ...154 5789 302 GB ...
Страница 155: ...155 5789 302 GB ...