Vitodens 200-W B2HB 45, 57 Installation
5680 493 - 05
36
Boiler Connections
System Layout 4
Vitodens 200-W, B2HB with...
- DHW storage tank
- one direct-connected heating circuit
- one heating circuit with a mixing valve
Installation of different heating circuits...
■
radiator heating circuit (high-temp. circuit)
■
under floor heating circuit with 3-way mixing valve
(low-temp.
circuit)
■
DHW
production
... with the following flow conditions:
1. The water flow rate (output) of the radiator heating
circuit is at least 30% greater than that of the under
floor heating circuit.
2. The total flow rate of the two heating circuits is
less than the maximum possible water flow rate of
the Vitodens 200-W B2HB boiler (see page 31 for
max. water flow rate).
The use of a low-loss header is strongly
recommended if the maximum water flow rate in the
application concerned exceeds the values shown on
page 31, or if the system flow rates are unknown.
The low-loss header is available as accessory part.
See following pages for additional installation examples
with a low-loss header.
The 3-way mixing valve, built-in to achieve the low-
temperature level of the under floor heating circuit, is
controlled by an accessory kit for a heating circuit with
mixing valve.
IMPORTANT
Legend
A
Vitodens 200-W B2HB boiler with
Vitotronic 200, HO1B outdoor reset
control
B
Outdoor temperature sensor
!
C
Vitotrol remote (optional)
D
Under floor heating circuit
E
Radiator heating circuit
F
Heating circuit pump
G
Mixing valve temperature sensor
?
H
Accessory kit for heating circuit with mixing valve
I
Domestic hot water storage tank
J
DHW tank temperature sensor
%
K
Expansion
tank
L
Temperature and pressure relief valve
M
Pressure relief valve
N
DHW recirculation pump
28/20
*
O
Boiler
pump
20
P
DHW circulating pump
sA
*
Function based on coding of address 33
DHW circulating pump
P
must pump into the Vitodens
200-W B2HB boiler (as illustrated).