NOTICE!
Leaky press connections due to pipes being too short
If two press connectors are to be mounted next to one
another onto a pipe without an interval, the pipe must not
be too short. If the pipe is not inserted up to the prescribed
insertion depth in the press connector during pressing, the
connection may become leaky.
d
12
15
18
22
28
35
Min‐
imum
interval
a [mm]
0
0
0
0
0
10
For the Z dimensions, refer to the respective product page in the online
catalogue.
3.3.5
Required tools
The following tools are required for production of a press connection:
n
pipe cutter or a fine-toothed hacksaw
n
deburrer and coloured pen for marking
n
press machine with constant pressing force
n
Press jaw or press ring with corresponding hinged adapter jaw, suit‐
able for the pipe diameter and suitable profile
Fig. 6: Press jaws
Interval between the pressings
Z dimensions