Error
Cause
Remedy
The magnet valve is
dirty or damaged.
Clean the magnet
valve, replace if
required.
The urinal flush runs
through.
The components have
been connected in the
wrong order.
Separate the plug
connections and wait
10 seconds. Re-con‐
nect the magnet valve
and then the power
supply.
The magnet valve is
dirty or damaged.
Clean the magnet
valve, replace if
required.
The control is defec‐
tive.
Replace the base
frame.
The red LED flashes
all the time.
The battery is weak.
Replace the battery.
3.5
Care and maintenance
3.5.1
Care tips
Use normal soap or a mild cleaning agent for regular care and preven‐
tion of lime scale on the flush plate. Under no circumstances should
scouring agent or scratching objects be used.
Strong stains can be removed using typical household cleaner. Rinse
the detergent thoroughly with clear water after the prescribed exposure
time. There should be no residue on the components.
Cleaning mode
Handling
Urinal flush plate for Prevista Visign for More 200 infrared flush actuation