Fault
Cause
Solution
After pressing, the press jaw
cannot be opened.
The pressing was unable to be
completed.
Press the Reset button and
remove the press jaw from the
press connector.
Check the press jaw and have
repaired as required.
Repeat the pressing*.
The press connector is incorrectly
pressed.
The press jaw dimension does not
match the press connector.
Use a press jaw that matches the
press connection dimension.
The press jaw was not positioned
square to the pipe axis on the
press connector.
Make sure that the press jaw is
positioned square to the pipe axis
on the press connector.
Repeat the pressing*.
The press contour is incorrect.
Check the press jaw and have
repaired as required.
Repeat the pressing* with an
operational press jaw.
The press machine has a fault.
**
Oil escapes from the press
machine.
A seal in the casing is faulty or
there is a mechanical problem.
**
The motor runs, but the press
machine does not complete the
pressing.
The oil level is too low.
* Remove the incorrectly or incompletely pressed press connector from the installation.
** Send the press machine to your nearest service partner for inspection and maintenance.
3.6
Care and maintenance
The tools are subject to normal wear and tear; for this reason, they must
be maintained in regular intervals. The maintenance and servicing of the
tools must be carried out by service partners authorised by Viega.
3.6.1
Cleaning the press tools
NOTICE!
Damage due to fluids!
Make sure that no fluids get inside the press machine.
Never dip the press machine into fluids.
Requirements:
Press machine
Handling
Pressgun Picco 6 press machine with battery
23