The WIO100 Input/Outputs module is one of the removable communication modules that can be 

installed on the W panel.

The WIO100 module has one programmable input and two programmable outputs.

WIth this module, the W panel can be connected to wired devices such as :

• 

Panic buttons, temperature sensors, safety light curtains, wired door contacts, glassbreak, shock, flooding or 
gas detectors (wired input).

• 

Flashing lights, spotlights, smoke equipment, light or sound indicator (wired output).

The programmable input can be configured as 

normally open

 (NO) or 

normally closed

 (NC), it can also be 

supervised 

in order to detect cable tampers. 

With the Mapping, the programmable input can be set up to take a 10 second video from any Videofied

®

 Motion Viewer™ 

when the detector linked to the programmable input is triggered.

The programmable input can also be wired to an existing alarm system in order to add video-vérification. That mode is 
called XTENDER mode.

Programmable outputs are normally open drys contacts that close when the output is activated.

Index

1.  Programmable input 2

1.1  Programmable input menu 2
1.2  Event list 3
1.3  Programmable input wiring and supervision 3
1.4  XTENDER Mode 4
1.5  XTENDER Mode configuration 5

2.  Programmable outputs 6

2.1  Programmable outputs triggering 6
2.2 Access to programmable outputs menu 7
2.3 Programmable outputs menu 7

W Panel 

www.videofied.com 

Doc. - Ref. 240-WIS100

Version : February 2015

A P P L I C A T I O N   N O T E

WIO 100 Input/Outputs module

Содержание WIO100

Страница 1: ...g the programmable input can be set up to take a 10 second video from any Videofied Motion Viewer when the detector linked to the programmable input is triggered The programmable input can also be wired to an existing alarm system in order to add video vérification That mode is called XTENDER mode Programmable outputs are normally open drys contacts that close when the output is activated Index 1 ...

Страница 2: ...tc You can find the event list on the next page Entry delay in seconds between the input triggering and the alarm triggering event transmission 0 3600 seconds Input Name This name can be seen by the monitoring center when the input triggers Choose a detailed name Siren type for the programmable input Siren the siren will be enabled and the keypad will beep Silent no siren no beeps Without siren on...

Страница 3: ...nked device triggering The security server will receive this event when the programmable input triggers Important These events are different from the events transmitted list in the FRONTEL SECURITY PARAMETERS menu They will be sent no matter how the events listed in the EVENT TRANS MODIFICATION are set 1 3 Programmable input wiring and supervision Programmable input wiring IN IN OUT1 OUTN OUT2 Pro...

Страница 4: ...the panel 4 W Panel www videofied com WIO 100 Input Outputs module When used in XTENDER mode arming devices keypads keyfobs badge readers cannot arm or disarm the system To switch between standalone mode and XTENDER mode go to the menu CONFIGURATION Lvl 4 GENERAL PARAMETERS XTENDER Note Enabling the programmable input will automatically disable the XTENDER mode and switch the W panel in standalone...

Страница 5: ... YES to select the parameter Enter the value for your Entry Delay up to 255 seconds and press OK or YES Note In From the Host mode the entry exit delay are managed by the master system Arming Confirmation is the number of seconds the system will wait to arm after voltage is latched on the arming input This feature can be used as an exit delay we suggest you to enter the same value as your master s...

Страница 6: ...UT 1 programmable output connection 2 Programmable outputs 2 1 Programmable outputs triggering INTRUSION TAMPER PANICBUTTON INCORRECTCODE DURESSCODE1 DURESSCODE2 SUPERVISION RADIOJAMMING LOWPANELBATT LOWDEVICEBATT ACPOWERMISS PANELRESET SYSTEMARMED SYSTEMDISARMED PERIODICTEST ALARMCANCEL SMOKEDETECTION PHONELINE MISS TMT REQUEST MEDICAL ASSIST ETHERNET CABLE DETECTION PROG INPUT1 You can find belo...

Страница 7: ...ammable output in cas of alarm EVENT TYPE INTRUSION Type of event assigned to the input intrusion smoke detection tamper assistance detection etc When the event occurs the output will activate OUTPUT NAME OUTPUT 1 Output name In order to recognize which system is connected to the output choose a detailed name 7 North American Headquarters 1375 Willow Lake Blvd Suite 103 Vadnais Heights MN 55110 US...

Отзывы: