26
Manual Titan
6. TECHNICAL
SPECIFICATIONS
6.1 General
Switch on behaviour
Charger can switch on under every load
Efficiency 24/80
24/100
48/50
85 % at 230Vac and 30Vdc 80A
85 % at 230Vac and 30Vdc 100A
85 % at 230Vac and 60Vdc 50A
Temperature range
0 °C until +40
°
C, decreasing output power if temperature
> +40
º
C
EMC
According Council Directive 89/336 EEG
Emission
EN 55014 (1993)
EN 61000-3-2 (1995)
EN 61000-3-3 (1995)
Immunity
EN 55104 (1995)
Vibration
IEC 68-2-6 (1982)
Safety
EN 60335-2-29 (1991)
6.2 Input
Input voltage range
185 - 265 Vac,
full output power available
Input voltage range 3-Ph
320 - 460 Vac 3-Ph, full output power available
Frequency range
45 - 65 Hz,
full output power available
Maximum Input current
model: 24/80
24/100
24/100 3-Ph
48/50
At 230V ac input voltage :
12A at 30V / 80A
16A at 30V / 100A
3x 3A at 30V / 100A
16A at 60V / 50A
Input fuse
model: 24/80
24/100,48/50
24/100 3-Ph
250Vac/8A and 12A fast 6,3x32mm, or equivalent
2 x 250Vac /12A
fast 6,3x32mm, or equivalent
2 x 250Vac /12A
fast 6,3x32mm, or equivalent
and 3-Ph MCB 6A B
Cos phi / power factor
1,0
6.3 Output
Model
TG 24/80
TG 24/100
TG 24/100
3-Ph
TG 48/50
Boost charge voltage
28,50 Vdc
28,50 Vdc
57 Vdc
Float charge voltage
26,50 Vdc
26,50 Vdc
53 Vdc
Output voltage range
24-33Vdc
24-33Vdc
48-66Vdc
Output voltage range supply
mode
2
0-33Vdc 0-33Vdc 0-66Vdc
Charge
characteristic
IUoUo IUoUo IUoUo
2
Contact your Victron Energy dealer for this option.