93
Default factory settings:
Repeated Absorption interval
7 days
Repeated Absorption time
4 quarters of an hour
Maximum Absorption time
4 hrs
Characteristic: Default = 3
1 = Fixed
Absorption time
Repeated Absorption interval
Repeated Absorption time
4 hrs
1 day
2 quarters
2 = Adaptive
3 = Adaptive with
Battery Safe Mode
Battery type: Default = 1
Abs. Voltage
Float Voltage / Reduced Float Max.Abs.time
0:User defined
1: Sonnenschein Dryfit A200 Gel
14.4 V
28.8 V
13.8 V / 13.0V 27.6 V / 26.0V
4 hrs
2: Traction (Tubular plate)
15.0 V
30.0 V
13.8 V / 13.0V 27.6 V / 26.0V
6 hrs
3: Semitraction
14.4 V
28.8 V
14.0 V / 13.0V 28.0 V / 26.0V
5 hrs
4: Victory
14.8 V
29.6 V
14.0 V / 13.0V 28.0 V / 26.0V
5 hrs
12V
model
24V
model
12V
model
24V
model
Factory defaults can always be restored by your authorized Victron Energy dealer. Acting sequence is
described in the installation part of the manual.