8
4. INSTALLATION
4.1 Location
The product must be installed in a dry and well-ventilated area, as close as possible to the
batteries. There should be a clear space of at least 10cm around the appliance for cooling.
For mounting see appendix F.
For safety purposes, this product should be installed in a heat-resistant
environment. Prevent the presence of e.g. chemicals, synthetic components,
curtains or other textiles, etc., in the immediate vicinity.
4.2 Connection of the Battery cables
In order to fully utilize the full capacity of the product, batteries with sufficient capacity and
battery cables with sufficient cross section should be used. See table:
48/800/9
24/800/16
12/800/35
Recommended cross
section (mm
2
)
1,5
5 m
10
16
25
Recommended battery
capacity (Ah)
20 – 100
40 – 200
100 – 400
Procedure
Proceed as follows to connect the battery cables:
Use an insulated box spanner in order to avoid shorting the battery.
Avoid shorting the battery cables.
Connect battery cables to the MultiPlus and battery, see appendix A.
Reverse polarity connection will cause damage to the product. (Safety fuse inside the
MultiPlus can be damaged)
This product should be installed by a qualified electrician.
a. Excessively high ambient temperature will result in the following:
- Reduced service life.
- Reduced charging current.
- Reduced peak capacity, or shutdown of the inverter.
b. Never mount the product directly above the batteries.
Содержание MultiPlus 12/800/35
Страница 22: ......
Страница 44: ......
Страница 66: ......
Страница 88: ......
Страница 110: ......
Страница 111: ...EN NL FR DE ES Appendix www victronenergy com Appendix A overview connections ...
Страница 113: ...EN NL FR DE ES Appendix www victronenergy com Appendix B installation information ...
Страница 117: ...EN NL FR DE ES Appendix www victronenergy com APPENDIX F dimensions ...
Страница 118: ......
Страница 119: ...www victronenergy com ...