5.5.3 Exemplary settings
Example 1 is the factory setting
ds-1
off
ds-2 Panel option
on
ds-3 Ch. voltage
off
ds-4 Ch. voltage
off
ds-5 Frequency
off
ds-6 Search mode
off
ds-7 AC-in Limit
off
ds-8 Store setting
→ ←
ds-1
off
ds-2
on
ds-3
off
ds-4
on
ds-5
off
ds-6
off
ds-7
on
ds-8
→ ←
ds-1
on
ds-2
off
ds-3
on
ds-4
on
ds-5
on
ds-6
on
ds-7
off
ds-8
→ ←
Example 1: (factory setting)
1
No panel or remote
switch connected
2
No panel or remote
switch connected
3, 4
GEL 14.4 V
5
Frequency: 60Hz
6
Search mode off
7
AC-in Limit 30 Amp
8
store setting: off
→
on
→ off
Example 2
1. No panel or remote
switch connected
2. No panel or remote
switch connected
3,4. AGM 14,7V
5. Frequency: 60Hz
6. Search mode off
7. AC-in Limit 50 Amp
8. store setting: off
→
on
→ off
Example 3
1. Panel or remote
switch connected
2. Panel or remote
switch connected
3, 4. Tubular plate 15V
5. Frequency: 50Hz
6. Search mode on
7. AC-in Limit 30Amp
8. store setting: off
→ on→
off
Store the settings (ds-3 to ds-7) by changing switch ds-8 from
‘off’ to ‘on’, and then back to
‘off’.
The LED’s ‘charger’ and ‘alarm’ will flash to indicate acceptance of the settings.
6 Maintenance
The Compact does not require specific maintenance. It will suffice to check all connections
once a year. Avoid moisture and oil/soot/vapours, and keep the device clean.
Содержание MultiPlus 12/3000/120-16
Страница 1: ...Manual EN Appendix MultiPlus Compact 12 2000 80 50 120V 24 2000 50 50 120V ...
Страница 2: ......
Страница 3: ......
Страница 34: ......
Страница 35: ...EN Appendix www victronenergy com APPENDIX A Connection overview ...
Страница 37: ...EN Appendix www victronenergy com APPENDIX B Installation information ...
Страница 38: ...APPENDIX C Parallel connection APPENDIX D Three phase connection ...
Страница 39: ...EN Appendix www victronenergy com APPENDIX E split phase connection ...
Страница 42: ......
Страница 43: ...www victronenergy com 255m m 125m m 520m m 95mm ...