5.5 Configuration with DIP switches
Some settings can be changed with DIP switches
Procedure:
a) Turn the Compact on, preferably without load and without AC voltage on the
inputs. The Compact will then operate in inverter mode.
b) Set the dipswitches as required.
c) Store the settings by moving Dip switch 8 to “on” and back to “off”.
5.5.1. DIP switch 1 and 2
Default setting: to operate the product with the “On/Off/Charger Only” switch
ds 1: “off”
ds 2: “on”
The default setting is required when using the “On/Off/Charger Only” switch in the front
panel.
Setting for remote operation with a Multi Control Panel:
ds 1: “on”
ds 2: “off”
This setting is required when a Multi Control Panel is connected.
The Multi Control panel must be connected to one of the two RJ48 sockets B, see appendix
A.
Setting for remote operation with a 3-way switch:
ds 1: “off”
ds 2: “off”
This setting is required when a 3-way switch is connected.
The 3-way switch must be wired to terminal L, see appendix A.
Only one remote control can be connected, i.e. either a switch or a remote control
panel.
In both cases the switch on the product itself should be “on”.
5.5.2. DIP switch 3 to 7
These DIP switches can be used to set:
- Battery charge voltage and Absorption time
- Inverter frequency
- Search mode
- AC input current limit 30A or 50A
Содержание MultiPlus 12/3000/120-16
Страница 1: ...Manual EN Appendix MultiPlus Compact 12 2000 80 50 120V 24 2000 50 50 120V ...
Страница 2: ......
Страница 3: ......
Страница 34: ......
Страница 35: ...EN Appendix www victronenergy com APPENDIX A Connection overview ...
Страница 37: ...EN Appendix www victronenergy com APPENDIX B Installation information ...
Страница 38: ...APPENDIX C Parallel connection APPENDIX D Three phase connection ...
Страница 39: ...EN Appendix www victronenergy com APPENDIX E split phase connection ...
Страница 42: ......
Страница 43: ...www victronenergy com 255m m 125m m 520m m 95mm ...