7
TEMPERATURE PROTECTION
The Lynx Ion + Shunt constantly monitors the battery temperatures, and protects them
according below rules. In case the temperature is outside the limits, it will first signal the
chargers and/or loads via the allow-to-charge and allow-to-discharge contacts. It will open
the safety contactor if there is no response. In that case you will see the LED blinking in the
specified error code ( see chapter 3 for details). Press the START-button to restart the
system.
High temperature signals:
•
Stop charging and discharging at +60°C (allow-to-charge and allow-to-discharge
contacts open)
•
Charge and discharge alarm at +65°C (safety contactor open)
Low temperature signals:
•
Stop charging at -5°C (allow-to-charge contact open)
•
Stop discharging at -20°C (allow-to-discharge contact open)
Alarm temperatures:
•
Charging alarm at -10°C and current > 10A (safety contactor open)
•
Discharging alarm at -25°C and current < -10A (safety contactor open)